5.1Standard setting
The COMPACT is delivered with the default setting following:
5.1.1Working mode
The working of the charger, the inverter and the transfer are described in chapter 5.3/5.4/5.5.
5.1.2Battery voltage
Low voltage | 11.6V / 23.2V / 46.4V |
Float Charge | 13.5V / 27.0V / 54.0V |
End of Charge Voltage | 14.4V / 28.8V / 57.6V |
Equalization | 15.3V / 30.6V / 61.2V |
Absorption Time: | 2 Hours |
5.1.3Auxiliary contact
Active in case of defect or manual turn off with the LED 10/11/12/13
5.2Reset value
When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always programmed with these standard settings.
In order to get to these settings during operation you must press the three Push Buttons 19/20/21 simultaneously for a minimum of 2 seconds.
5.3Battery voltages and absorption time
The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance with the diagram shown below:
5.3.1Table of voltage and timing threshold
| Low voltage |
| Float Charge | Absorption |
| Equalization |
| Absorpt. | |||||
| LED 13 |
| LED 12 |
| LED 11 |
| LED 10 |
| Time | ||||
|
|
|
|
|
|
|
|
|
|
|
|
| LED |
LED | 12V | 24V | 48V | 12V | 24V | 48V | 12V | 24V | 48V | 12V | 24V | 48V | 12/24/48V |
14 | 12.0 | 24.0 | 48.0 | 13.7 | 27.4 | 54.8 | 16.2 | 32.4 | 64.8 | 16.2 | 32.4 | 64.8 | 4 h |
15 | 11.8 | 23.6 | 47.2 | 13.6 | 27.2 | 54.4 | 15.6 | 31.2 | 62.4 | 15.9 | 31.8 | 63.6 | 3 h |
16 | 11.6 | 23.2 | 46.4 | 13.5 | 27.0 | 54.0 | 15 | 30 | 60 | 15.6 | 31.2 | 62.4 | 2 h |
17 | 11.4 | 22.8 | 45.6 | 13.4 | 26.8 | 53.6 | 14.4 | 28.8 | 57.6 | 15.3 | 30.6 | 61.2 | 1 h |
18 | 11.2 | 22.4 | 44.8 | 13.3 | 26.6 | 53.2 | 14.2 | 28.4 | 56.8 | 15 | 30 | 60 | 0 – 1Min. |
The heavy printed values show the standard settings.