POWER TO THE FIREPLACE The Optional Blower Kit Operates on 115 volt 60 Hz 150 watts AC

HOUSE

WIRING

 

GROUND

 

WIRE

 

COVER PLATE

House Wiring Must Be Secured

Replace Cover Plate

With The Appropriate Electrical

After Electrical

Connector To The Fireplace

Hook-Up

Convenience Outlet Wiring

 

Figure 42

BLOWER THREE

PRONGED PLUG TO

GROUNDED OUTLET

Figure 43

The FBK-100/200 Blower Kits are design certi- fied by Warnock Hersey for use with these appliances.

Always check local building codes. Installation of the FBK Blower Kits must comply with local regulations as well as the National Electric Code.

Combustion Air Kits

These appliances are equipped with an outside (make-up) air door and integral actuator arm. If the appliance is to be installed with an outside air vent system, use only FireCraft Models FAOK or FAOK-LD Combustion Air Kits. These kits come complete with detailed installation instructions and all components necessary in completing a combustion air vent system.

After completing the installation of the optional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclo- sure around the firebox. Failure to do so may result in extensive and costly rework.

Locate the actuator arm along the right side of the appliance firebox opening and refer to Figure 44. After completing the installation of the Outside Combustion Air Kit remove and discard the actuator arm locking screw.

WARNING: DO NOT REMOVE THE AC- TUATOR ARM LOCKING SCREW UNLESS THE COMPLETE OUTSIDE AIR VENT SYS- TEM HAS BEEN INSTALLED IN ACCOR- DANCE WITH THE DETAILED INSTRUC- TIONS PROVIDED WITH THE KIT.

Combustion

Air Actuator

Pull Forward to Open,

Push Back to Close

Figure 44

To operate, push the end of the actuator to the left as shown in Figure 44, until it "pops" free of its "locked" position. Pull the actuator forward to open the combustion air door, and push it back to close. To "lock" the combustion air door closed, ensure the actuator is pushed all the way back then push the end of the actuators to the right until the step in the actuator moves behind the appliance front face within the slot- ted opening.

Operate the actuator through several cycles including the "lock position. Ensuring proper operation and freedom of movement. Return the actuator arm to the locked position.

Gas Line Connection

Install a 1/2" gas supply line through fireplace wall for connection to a decorative gas appli- ance inside the firebox. Outside, the gas supply line connects to a gas shut-off valve recessed flush into the wall or floor. The valve should be controlled by a removable valve key for safety.

Always plumb gas line installation per local codes. Check all connections with soap suds; leaks will bubble. Never test any gas line con- nection with a match or open flame.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

This provision is intended for connection to a decorative gas appliance incorporating an au- tomatic shut-off device and complying with the Standard for Decorative Gas Appliances for installation in vented fireplaces, ANSI Z21.60 (1991) or American Gas Association draft re- quirements for Gas-Fired Log Lighters for Wood Burning Fireplaces, Draft No. 4 dated August, 1993. Install in accordance with the National Fuel Gas Code, ANSI Z223.1. This complies with the revised U.L. 127 standard.

Vent Free Appliances

This unit has been tested and approved to ANSI/IAS/AGA Z21.11.2 for use with unvented gas appliances and complies with the stan- dard for Factory-Built fireplaces, UL 127, when installed with unvented gas log sets. Special instructions with regards to mantle installa- tions must be taken into consideration when installing such appliances.

The unit has been tested for use with any unvented log sets having a maximum rating of 26,000 BTU. The minimum mantle configura- tion for these log sets are outlined in Figure 46.

Log sets with 40,000 BTU may be installed provided that no combustible mantle projec- tions are placed lower than 18 inches from the fireplace opening.

These fireplaces have been marked with a maximum rating of 26,000 BTU to assure that homeowners do not exceed the allowable lim- its for all allowed installations of mantles. That limit may be increased to 40,000 BTU, pro- vided that the mantle installed complies with the 18-inch limitation and a copy of these instructions are available.

NEVER INSTALL AN UNVENTED GAS LOG SET WITH A BTU GREATER THAN 26,000 IF COMBUSTIBLE MANTLE PROJECTIONS ARE LOWER THAN 18 INCHES ABOVE THE FIRE- PLACE OPENING.

WARNING: MODELS THAT HAVE THE "-2" SUFFIX HAVE NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN UNVENTED GAS LOG SET INTO THIS FIREPLACE.

CAUTION: WHEN USING THE DECORATIVE GAS APPLIANCE, THE FIREPLACE DAMPER MUST BE SET IN THE FULLY OPEN POSITION.

CAUTION: PLUMBING CONNECTIONS SHOULD ONLY BE PERFORMED BY A QUALIFIED, LI- CENSED PLUMBER. MAIN GAS SUPPLY MUST BE OFF WHEN PLUMBING GAS LINE TO FIRE- PLACE OR PERFORMING SERVICE.

15

Page 15
Image 15
Superior BC-36-2, BCI-36, BR-36-2 installation instructions Combustion Air Kits, Gas Line Connection, Vent Free Appliances