Therma-Stor Products Group XT150H For Hvac Installer And Homeowner, Auxiliary relay operation

Models: XT150H

1 28
Download 28 pages 13.05 Kb
Page 12
Image 12
FOR HVAC INSTALLER AND HOMEOWNER

FOR HVAC INSTALLER AND HOMEOWNER

WARNING: TO AVOID TRANSFORMER DAMAGE ONLY CONNECT THE WHITE WIRE TO THE CONTROL IF A DAMPER IS USED.

The white wire controls the optional motorized damper that can be installed into a fresh air duct. This provides the ability to control when fresh air is introduced into the building by using the ventilation timer function labeled “DMP” on the control (See Section 3.7). IF THE MOTORIZED DAMPER IS

NOT USED, DO NOT CONNECT THE WHITE WIRE TO THE CONTROL OR DAMAGE TO THE TRANSFORMER MAY RESULT. Simply leave the (DMP) terminal unused if the damper is not used, and cap off the white lead from the Ultra- Aire dehumidifier.

2.3 Auxiliary relay operation

At times it may be desirable to coordinate fan operation of the central heating/cooling system with dehumidifier operation. The DEH 3000 features a relay that provides this ability. The relay terminals labeled NC, COM and NO operate according to the following chart:

Dehumidification

 

 

Operation

COM/NO

COM/NC

 

 

 

ON

CLOSED

OPEN

OFF

OPEN

CLOSED

Common uses (assuming standard thermostat wiring color schemes as noted):

Disengage A/C during dehumidification

Redirect the yellow thermostat wire to the NC terminal. Wire the yellow wire from the A/C to the COM terminal.

Engage the A/C central fan during dehumidification

1.Disconnect the green wire that runs to the fan relay from the screw on the thermostat.

2.Connect the green wire that runs to the fan relay to the COM screw on the DEH3000 board.

3.Run a wire from the red wire screw on the thermostat to the NO (Normally Open) screw on the DEH3000 board.

4.Run a wire from the green wire screw on the thermostat to the NC (Normally Closed) screw on the DEH3000 board.

The central fan should run when the Thermostat fan switch is turned to ON and when the dehumidifier is operating.

2.4Dehumidifier lockout/activation: AC sensor feature

The control has the ability to activate the dehumidifier or deactivate the dehumidifier when the air conditioner is running.

Standard wire colors for thermostats are as follows:

Description

Color

Terminal code

 

 

 

24VAC Return

Red

R

 

 

 

Call for Heat

White

W or W1

 

 

 

Force Fan On

Green

G

 

 

 

Compressor

 

 

Call for Cooling

Yellow

Y or Y1

 

 

 

12

Ultra-Aire XT150H Installer’s & Owner’s Manual

Page 12
Image 12