OMC/GMC TROUBLESHOOTING FLOWCHART

All installations and services must be performed by qualified service personnel.

OMC/GMC TROUBLESHOOTING FLOWCHART

Set thermostat subbase to "HEAT"

Does thermostat make contact?

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Is room temperature

 

Yes

 

 

Wait for room air to cool.

 

above 90 deg. F?

 

 

 

 

Yes

No

Yes

 

Is room temperature above

Turn thermostat setting

thermostat setting?

 

above room temp.

No

Replace thermostat

Does a "call for heat" initiate an ignition cycle?

Yes

No

 

 

 

 

Yes

 

 

 

 

Is the power switch "off"?

 

 

Turn power

 

 

 

 

 

 

 

 

 

 

switch "on".

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

Check input power. Reset circiut

 

Is there 120 VAC

 

 

 

 

breaker, or replace blown fuse in

 

across lines L1 & L2?

 

 

 

 

 

disconnected switch.

 

 

 

 

 

 

 

Yes

 

 

 

Wait for furnace to cool.

 

 

 

 

Is the control transformer

No

Have either of the

Yes

Look for cause(s) of high

limit activation,eg. low

(GMC) or oil primary control

 

high limit thermostats

 

 

 

airflow, over-firing,

(OMC) receiving 120 VAC?

 

activated?

 

 

 

blocked flue,etc..

 

 

 

 

 

 

 

 

Correct any

 

 

 

 

abnormal conditions.

Yes

 

No

 

 

 

 

With power on,measure

 

 

 

voltage across the aux.

 

 

 

high limit thermostat N.C.

 

 

 

contact to L2. If not 120 VAC,

 

 

 

replace aux. high limit

 

 

 

 

thermostat. Else,replace

 

 

 

high limit thermostat.

 

 