All installations and services must be performed by qualified service personnel.
|
|
|
|
| No |
|
|
| Are the thermostat wires |
|
| ||
|
|
|
|
| ||
|
| connected properly? |
|
|
| |
|
|
|
|
|
|
|
|
|
| Yes |
|
| |
Yes |
|
|
|
|
|
|
| Is the transformer (GMC) or | Yes | ||||
|
| |||||
|
| oil primary control (OMC) | ||||
|
|
|
| |||
|
| supplying 24 VAC to the |
|
| ||
|
| thermostat? |
|
|
No |
Replace control transformer (GMC)
or try resetting the oil primary control (OMC). Replace the oil primary control, if necessary.
Correct wire connections.
Replace thermostat.
Is there combustion
airflow to the furnace?
Yes
|
|
| On the GMC,has 1 TDR |
|
|
| activated and closed the |
No |
| No | output relay contacts? |
Is there 120 VAC across | If not, replace 1 TDR. On | ||
|
| OMC, is the oil primary | |
| the burner motor? |
| |
|
| control receiving power? | |
|
|
| |
|
|
| Reset primary control. If |
|
|
| resetting the primary does |
|
|
| not work, replace control. |
| Yes |
|
|
| Is the blower impeller spinning? |
|
|
| If so, check for blockages in or a |
|
|
| collapsed air duct. Is the air boot |
|
|
| shutter open adequately. |
|
|
Yes |
Check wiring to burner motor. If okay, replace burner motor.
33