All installations and services must be performed by qualified service personnel.
The temperature rise across the furnace heat exchanger operating at
: If the temperature rise exceeds 100°F, the heat exchanger may fail, voiding the heat exchanger warranty resulting in property damage, personal injury or loss of life.
M. FLUE GAS COMBUSTION ANALYSIS
: Burner adjustments must be confirmed by instrumentation. Failure to use accurate or calibrated instrumentation to correctly setup the burner may result in reduced efficiency, sooting, and/or the production of hazardous carbon monoxide gas.
For typical burner combustion analysis results, refer to the table below.
BURNER COMBUSTION PARAMETERS
FURNACE MODEL |
| |||
FUEL TYPE | #1 OR #2 FUEL OIL | NATURAL GAS | PROPANE GAS | |
CO (CARBON MONOXIDE) | 50PPM OR LESS | 50PPM OR LESS | 50PPM OR LESS | |
CO2 (CARBON DIOXIDE) |
| |||
O2 (OXYGEN) |
| |||
SMOKE SPOT RATING | 0 TO TRACE | N/A | N/A | |
AIR SHUTTER | OPEN TO | OPEN TO | OPEN TO | |
ADJUSTMENT | POSITION 35 | POSITION 4 | POSITION 4 |
N/A = NOT APPLICABLE