Thermo Products PGL33-250, PGT16-160, PGT5-100 M. Filters, A. Pgt Horizontal Units B. Pgl Lowboy

Models: PGL33-250 PGL39-400 PGL37-312 PGT11-125 PGL20-180 PGT5-100 PGT16-160

1 38
Download 38 pages 37.07 Kb
Page 20
Image 20
M. FILTERS

All installations and services must be performed by qualified service personnel.

A. 400 CFM X 3 TON (36,000 BTU'S) = 1,200 CFM FOR COOLING

B. 400 CFM X 2.5 TON (30,000 BTU'S) = 1,000 CFM FOR COOLING

NOTE: To obtain the proper 50°F to 80°F temperature rise for heating an air conditioning coil is installed, the speed of the blower motor may have to be changed. This depends on the static resistance of an individual duct system and the size of the air conditioner.

M. FILTERS

To clean a dirty filter, first remove the blower compartment door. Remove dirty filter from the filter rack and clean with a mild soap and water solution. Make sure filter is thoroughly dry before replacing. Put blower compartment door back into place.

A. PGT HORIZONTAL UNITS

B. PGL LOWBOY

18

Page 20
Image 20
Thermo Products PGL33-250, PGT16-160, PGT5-100, PGL20-180, PGT11-125 M. Filters, A. Pgt Horizontal Units B. Pgl Lowboy