Thomas & Betts RZ-NA 441-OMS Controls - Location, Operation, and Service, Cabinet

Models: RZ-NA 441-OMS

1 12
Download 12 pages 45.26 Kb
Page 5
Image 5
Operation/Service Section

Operation/Service Section

Controls - Location, Operation, and Service

To service this system, it is necessary to understand the normal operation of the controls and the function of the diagnostic circuit board. Refer to the electrical box drawing in Figure 7 and to the individual illustrations to identify and locate each of the controls. The wiring diagrams for this unit are located in the main electrical box.

WARNING: Service work on this system should only be done by a qualified gas ser- vice person. The service information and the troubleshooting guides are intended as an aid to a qualified service person.

Figure 7 - Control Locations

Control

Outside Air Cutoff

Time Delay

 

Relays

(high ambient limit control)

Relay

24-volt Terminals

Ignition

Module

Maxitrol Amplifier

Circuit

or Signal Conditioner

Board

 

Bypass

Damper

Motor

Status Lights

-Volt Terminals

Transformer

Service

Switches

24

 

Return

Air

Damper

Motor

Motor

Starter

High Controls - Location, Operation, and Service7.Electronic Circuit Board with Diagnostic Lights8. Temperature Limit Safety Controls• Manual Reset Limit Control - Blower LowCabinet

Optional

Optional Bypass Damper

Standard Pressure

Relay for

Dirty Filter

Pressure Switches

Switches

Optional 2-Speed

Pressure Switch

 

 

 

NOTE: Wiring diagrams for the unit are located on the inside of the electrical box door.

Starter

Line Voltage

Relay

Terminals

7.Electronic Circuit Board with Diagnostic Lights

Location: Control Compartment Electrical Box (See Figure 7)

Function: The diagnostic lights on the circuit board are designed to assist in troubleshooting. When the system is operating properly, the lights on the circuit board are lit. If the system fails to operate properly, all lights on the circuit board up to that one that represents the component or system that has failed will be lit. For more detailed information, refer to the Trouble- shooting Guide in Paragraph 19.

Figure 8 -

 

 

 

 

Diagnostic

 

 

Column of 13

Circuit

Board,

indicator

P/N 151263

bulbs; always

 

replace

 

burned out

 

bulbs, P/N

 

125189.

8. Temperature Limit Safety Controls

Location: 1) Manual Reset Limit Switch is mounted on a 2x4 electrical box located in the blower section. To access the manual reset, remove the blower section access panel to the left of the discharge (left when facing the discharge); 2) Emergency Cutoff Limit Control is in the burner/control cabinet just above the electri- cal box.

• Manual Reset Limit Control - Blower

Cabinet

 

Figure 9 -

Function: The

Manual Reset

manual reset limit

Limit

is a temperature

 

activated safety

Capillary tubing is

control. Re-start

in a holder that

of the system can

extends into the

be done only after

the limit control is

 

cooled and the reset button is depressed.

CAUTION: If the manual reset limit activates, find and correct the cause before re-starting the system.

Service: Failure of the manual reset limit requires replacement of the control.

Page 5

Page 5
Image 5
Thomas & Betts RZ-NA 441-OMS Controls - Location, Operation, and Service, Electronic Circuit Board with Diagnostic Lights