Chapter 4: SYSTEM SETTINGS (SETTING USING BROWSER)
(2) Type
Select from [Momentary] and [Latch].
Momentary: Provides output during the period between receiving an activation request and receiving a
stop request.
Latch: Provides 1 second of output upon receiving an activation request and 1 second of output
upon receiving a stop request.
Note
[Latch] cannot be selected when setting Mode to [STATUS Output] or [ERROR Output].
1 s
1 s
Broadcast and
activation data
Contact output
Contact output
Make
Break
• Latch
Broadcast and
activation data
Contact output
Contact output
Make
Break
• Momentary
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Activation Stop
Activation Stop
Caution
The unit's correct operation cannot be ensured if both activation and stop signals
are received during the 1-second output interval.
(3) Polarity
Select Polarity from [Make] and [Break].
Make: ON when the contact is closed.
Break: ON when the contact is opened.
(4) Contact OFF Delay Time [sec]
Enter an OFF delay time of 0 – 60 seconds for the duration between receiving a termination request and
actually turning OFF the contact. When in Resend mode and making broadcasts with longer delay times,
set the OFF delay time to correspond to the delay time.
Note
For more information regarding OFF delay time, refer to p.6-4.
(5) Save button
Updates the NX-100/100S setting file.
Caution
Never restart the unit or turn off the power during updates, or while the STATUS indicator on the front
panel of the NX-100/100S is flashing.