1600EP Single Phase Uninterruptible Power Supply Systems Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
6.0 | UPS Output |
|
|
|
| Voltage: | 240/208/120 VAC Single Phase |
| |
| Capacity: | kVA | kW (@ 0.85PF) |
|
|
| 3.6 kVA | 3.1 kW |
|
|
| 6.0 kVA | 5.1 kW |
|
|
| 8.0 kVA | 6.8 kW |
|
|
| 10.0 kVA | 8.5 kW |
|
|
| 14.0 kVA | 11.9 kW |
|
|
| 18.0 kVA | 15.3 kW |
|
|
| 22.0 kVA | 18.7 kW |
|
| Regulation: | |||
| Distortion: | Less than 6% THD at Full | ||
|
| Less than 3% THD at full Linear Load |
| |
| Step Load: | ± 8 % max from 100% to 0 % or from 0% to 100 % linear load | ||
| Output Current: | kVA | RMS | PEAK |
|
| 3.6 | 15.0A | 45.0A |
|
| 6.0 | 25.0A | 75.0A |
|
| 8.0 | 33.3A | 100.0A |
|
| 10.0 | 41.6A | 125.0A |
|
| 14.0 | 58.0A | 174.0A |
|
| 18.0 | 75.0A | 225.0A |
|
| 22.0 | 91.6A | 275.0A |
Overload Capacity (Inverter): 150% for 10 seconds 125% for 30 seconds 1000% for 1 cycle
Crest Factor: | 3.0 |
Frequency: | 50/60Hz Auto Sensing |
Regulation: | ± 0.5Hz / ±1.0Hz / ±1.5Hz (authorized service center selectable only) |
Synchronous Range: +/- 1 Hz
Wave Form: Sine wave, Zero Transfer Time
Load Power Factor: | 0.85 lagging (0.6 to 1.0) |
Efficiency AC to AC: Greater than 83%
Page 3 of 8