1600EP Single Phase Uninterruptible Power Supply Systems Guide Specifications

3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA

9.0Dimensions

 

3.6 kVA

6.0 kVA

8.0 - 10 kVA

14 - 22kVA

Weight

322 lbs

346 lbs

476 lbs

784 lbs

Depth

28”

28”

28”

39"

Width

10”

10”

13”

18"

Height

33”

33”

34”

35"

Casters and leveling feet are standard

10.0Communications

10.1Dry Contact Communication

The remote interface is a standard feature. Signals are available through a DB9 male connector.

1)AC input present

2)Battery operation

3)Inverter

4)Bypass active

5)Fault

6)Loss of utility

10.2RS-232C Communication

The RS-232C serial communication interface is available through a DB9 female connector. The interface allows control of the UPS from a personal computer running special Toshiba software.

10.3EPO Control

The UPS shall come with terminals on its rear side for receiving an Emergency Power Off (EPO) and Remote Run/Stop command from a remote locations.

11.0Reliability

Demonstrated mean time between failures (MTBF) of 200,000 hours.

12.0 Environment Operation

 

 

Operating Ambient Temperature:

0 ~ 40oC (32 ~ 104oF)

Recommended Temperature:

+15oC ~ 25oC

Storage Temperature:

-20oC ~ 40oC

Humidity:

30-90%, Non-Condensing

Audible Noise:

50dB (A) maximum @ 1 meter from Front Panel