1600EP Single Phase Uninterruptible Power Supply Systems Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
9.0Dimensions
| 3.6 kVA | 6.0 kVA | 8.0 - 10 kVA | 14 - 22kVA |
Weight | 322 lbs | 346 lbs | 476 lbs | 784 lbs |
Depth | 28” | 28” | 28” | 39" |
Width | 10” | 10” | 13” | 18" |
Height | 33” | 33” | 34” | 35" |
Casters and leveling feet are standard
10.0Communications
10.1Dry Contact Communication
The remote interface is a standard feature. Signals are available through a DB9 male connector.
1)AC input present
2)Battery operation
3)Inverter
4)Bypass active
5)Fault
6)Loss of utility
10.2
The
10.3EPO Control
The UPS shall come with terminals on its rear side for receiving an Emergency Power Off (EPO) and Remote Run/Stop command from a remote locations.
11.0Reliability
Demonstrated mean time between failures (MTBF) of 200,000 hours.
12.0 Environment Operation |
|
|
Operating Ambient Temperature: | 0 ~ 40oC (32 ~ 104oF) | |
Recommended Temperature: | +15oC ~ 25oC | |
Storage Temperature: | ||
Humidity: | ||
Audible Noise: | 50dB (A) maximum @ 1 meter from Front Panel |
Page 6 of 8