1600EP Single Phase Uninterruptible Power Supply Systems Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
Noise Isolation: Neutral is bonded to ground on the output of the Isolation | transformer | |
for isolation of common mode |
| |
Bypass: | Manual bypass provided with switch with less than 4 ms transfer |
7.0 | UPS Battery |
|
|
| Battery Bus Volts: |
| |
| 3.6 kVA | 216 VDC nominal | |
| 6.0 kVA | 216 VDC nominal | |
| 8.0 kVA | 288 VDC nominal | |
| 10.0 kVA | 288 VDC nominal | |
| 14.0 kVA | 288 VDC nominal | |
| 18.0 kVA | 288 VDC nominal | |
| 22.0 kVA | 288 VDC nominal | |
| Backup time: | 0.7PF | 0.85PF |
| 3.6 kVA | 14 minutes | 10 minutes |
| 6.0 kVA | 7 minutes | 7 minutes |
| 8.0 kVA | 7 minutes | 7 minutes |
| 10.0 kVA | 5 minutes | 5 minutes |
| 14.0 kVA | 7 minutes | 7 minutes |
| 18.0 kVA | 5 minutes | 5 minutes |
| 22.0 kVA | 5 minutes | 5 minutes |
Type of Battery: | Enersys | |
Number of Battery: | Six batteries in each pack | |
Average Recharge: | 24 hours (12 hours for 90%) | |
Battery Voltage Range: | ||
3.6 kVA | 170 | – 245.7 VDC |
6.0 kVA | 170 | – 245.7 VDC |
8.0 kVA | 227 | - 327 VDC |
10.0 kVA | 227 | - 327 VDC |
14.0 kVA | 227 | - 327 VDC |
18.0 kVA | 227 | - 327 VDC |
22.0 kVA | 227 | - 327 VDC |
Cutoff Voltage: 1.6 | Volts per cell |
|
Heat Generation | kVA | BTU / Hour |
| 3.6 | 1588 |
| 6.0 | 2610 |
| 8.0 | 3482 |
| 10.0 | 4352 |
| 14.0 | 6092 |
| 18.0 | 7832 |
22.09600