System Fault Messages
A Fault message is generated when either a fault condition occurs, or a warning condition occurs three times within ten minutes. The table below shows the possible fault messages and what actions need be taken.
If the input voltage is normal when the fault occurs then the UPS will switch immediately to the bypass mode to continuously feed power to the load.
If the fault condition occurs while the input power is abnormal and the UPS is in Bypass mode the UPS will shut down the output to prevent load equipment damage.
When a Fault condition exists, the red LED on the UPS display panel will illuminate until the fault is cleared.
Display | Meaning | Action |
BYPOH | Bypass Overheat – Overheating | Check unit for blocked or |
| condition occurred. | bient temperature if it is greater than 104 °F (40 °C). |
|
| Bypass operation will also cease if overheat condition |
|
| is not corrected within 1 hr. of inverter shutdown. Try |
|
| restarting. If condition |
|
| down and call for service. |
BYPOL | Bypass Overload – UPS is over- | Shut down excess equipment to reduce load. |
| loaded. |
|
CHRGOV | Charger Overvoltage – Charger | UPS is possibly faulty. Check the UPS operation |
| overvoltage condition occurred. | conditions at time of fault. Not advisable to restart the |
|
| UPS. Call for service. |
CLMT | Current Limit – Load on UPS out- | Reduce load on UPS output. |
| put exceeds unit specifications. |
|
DCIB | DC Bus Imbalance – DC voltage | Possible causes are UPS fault are connection of half- |
| imbalance occurred. | wave rectifier load. Check load and try restarting. If |
|
| condition persists, call for service. |
DCOC | DC Bus Overcurrent – DC overcur- | UPS is possibly faulty. Check the UPS operation |
| rent condition occurred. | conditions at time of fault. Not advisable to restart the |
|
| UPS. Call for service. |
DCOV | DC Bus Overvoltage – DC over- | UPS is possible faulty, input wiring error, input over- |
| voltage condition occurred. | voltage or connection of a motor load. Try restarting. If |
|
| condition persists call for service. |
DCUVBS | DC Bus Undervoltage during | UPS is possibly faulty. Check the UPS operation |
| Boostup Mode – DC Bus under- | conditions at time of fault. Not advisable to restart the |
| voltage condition occurred. | UPS. Call for service. |
DCUVC | DC Bus Undervoltage During | UPS is possibly faulty. Check the UPS operation |
| Charging Mode – DC Bus under- | conditions at time of fault. Not advisable to restart the |
| voltage condition occurred. | UPS. Call for service. |
DVCOH | Device Overheat – Overheating | Reduce equipment load to 100% or less and try |
| condition occurred. | restarting. |
FSOPEN | Fuse Open. | Replace fuse. |
INVOLNR | Inverter Overload (Not Reset- | Reduce equipment load to 100% or less and manually |
| table) – Output overload condition | restart the UPS. |
| occurred. |
|
62 | 1600XP Series Installation and Operation Manual |