11.111.111.111.1 ReadReadReadRead----Only RegistersOnly RegistersOnly RegistersOnly Registers Register Bit Function Bank Mask Adjustment Range Multiplier
01 ∼ 09 word Reserved
0A word RX terminal analog input
value 0 FFFF 0000 ~ 7FFF (-100% ~ 0% )
7FFF ~ FFFF (0% ~ 100%) 1
0B word Frequency command
monitor 0 FFFF
0000 ∼ 9C40
(0.00 ∼ 400.00 Hz) 0.01
0C word
Input voltage monitor(Note 1) 0 FFFF 0 ~ 255% 0.1
0D word Output terminal status
monitor 0 00FF Refer to Table 4 (page 32)
0E word Inverter Status 1 0 FFFF Refer t o Table 5 (page 32)
0F word Inverter Status 2 0 00FF Refer to Table 6 (page 32)
10 word Present trip 0 00FF
11 high
byte 4th Past trip (most recent) 0 7F00
low
byte 3rd past trip 007F Refer to section 11.3 for fault
codes
12 high
byte 2nd past trip 0 7F00
low
byte 1st past trip (oldest) 007F
13 word Pre-compensation output
frequency 0 FFFF
0000 ∼ 9C40
(0.00 ∼ 400.00 Hz) 0.01
14 word Post-compensation output
frequency 0 FFFF
0000 ∼ 9C40
(0.00 ∼ 400.00 Hz) 0.01
15 word Torque current monitor 0 FFFF
(Note 2) 0.01
16 word Excitation current monitor 0 00FF
00 ∼ FF (0 ~ 255%) 1
17 word PID feedback value 0 FFFF
(Note 2) 0.02
18 word Motor overload ratio 0 FFFF 0 ~ 65535 100/65535
19 word Inverter overload ratio 0 FFFF 0 ~ 65535 100/65535
1A word DBR overload ratio 0 FFFF 0 ~ 65535 100/65535
1B word Input power (%) 0 FFFF 0 ~ 6553.5 0.1
1C word Input power (kW) 0 FFFF (Note 3)
1D word Output power (%) 0 FFFF (Note 2) 0.1
1E word Output power (kW) 0 FFFF (Note 2, Note 3)
1F, 20 word Reserved
21 word Input / output power units 0 0008 0000: 0.01kW
0008: 0.1kW
22 word Command mode status 0 0003 0000: terminal
0001: panel
0002: option
0003: RS232C
23 word Frequency mode selection
status 0 000C 0000: terminal
0004: panel
0008: option
000C: RS232C
24 low
byte Profibus interface card
software revision
high
byte Profibus interface card
software version
25 word Output current (amps) FFFF 0.0 ~ 6553.5 A 0.1
(Note 1) These monitor voltage units are not aff ected by the setting of VOLTAGE UNITS SELECTION in
GROUP:UTILITY PARAMETERS; they are always in units of %.
(Note 2) These registers use signed data (data values l arger t han 7FFF H are negat ive). If the register data is
8000H or larger, the actual value can be obtained by: actual value = - [FFFFH - (register data) + 1].