11.2.611.2.611.2.611.2.6 GROUP:FREQUENCY SETTING PARAMETERSGROUP:FREQUENCY SETTING PARAMETERSGROUP:FREQUENCY SETTING PARAMETERSGROUP:FREQUENCY SETTING PARAMETERS Register Function / Title Bank Mask Adjustment Range Multiplier
81 FREQUENCY PRIORITY
SELECTION #1 0 / 1 0007 0001: RR (1)
0002: IV (2)
0003: RX (3)
0004: PG (4)
0005: BIN (5)
82 FREQUENCY PRIORITY
SELECTION #2 0 / 1 0038 0008: RR (1)
0010: IV (2)
0018: RX (3)
0020: PG (4)
0028: BIN (5)
83 ANALOG INPUT FILTER 0 / 1 0003 0000: No filter (0)
0001: Small filter (1)
0002: Medium filter (2)
0003: Large filter (3)
84 RR TERMINAL STANDARD
OR ADJUSTABLE 0 / 1 0002 0000: Standard (0)
0002: Adjustable (1)
85 1
RR REFERENCE
SETTING POINT #1 0 / 1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
86 RR REF POINT #1
FREQUENCY 0 / 1 FFFF 0000 ∼ Fmax 0.01
87 RR REFERENCE
SETTING POINT #2 0 / 1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
88 RR REF POINT #2
FREQUENCY 0 / 1 FFFF 0000 ∼ Fmax 0.01
89 IV TERMINAL STANDARD
OR ADJUSTABLE 0 / 1 0004 0000: Standard (0)
0004: Adjustable (1)
8A 1
IV REFERENCE
SETTING POINT #1 0 / 1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
8B IV REF POINT #1
FREQUENCY 0 / 1 FFFF 0000 ∼ Fmax 0.01
8C IV REFERENCE
SETTING POINT #2 0 / 1 00FF 0000 ∼ 0064 (0 ∼ 100) 1
8D IV REF POINT #2
FREQUENCY 0 / 1 FFFF 0000 ∼ Fmax 0.01
8E RX TERMINAL STANDARD
OR ADJUSTABLE 0 / 1 0008 0000: Standard (0)
0008: Adjustable (1)
8F 1
RX REFERENCE
SETTING POINT #1 0 / 1 00FF 009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
1
90 RX REF POINT #1
FREQUENCY 0 / 1 FFFF -Fmax ∼ Fmax 0.02
91 RX REFERENCE
SETTING POINT #2 0 / 1 00FF 009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
1
92 RX REF POINT #2
FREQUENCY 0 / 1 FFFF -Fmax ∼ Fmax 0.02
93 PG TERMINAL STANDARD
OR ADJUSTABLE 0 / 1 0010 0000: Standard (0)
0010: Adjustable (1)
94 1
PG REFERENCE
SETTING POINT #1 0 / 1 00FF 009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
1
95 PG REF POINT #1
FREQUENCY 0 / 1 FFFF -Fmax ∼ Fmax 0.02
96 PG REFERENCE
SETTING POINT #2 0 / 1 00FF 009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
1
97 PG REF POINT #2
FREQUENCY 0 / 1 FFFF -Fmax ∼ Fmax 0.02