44
Register Function / Title Bank Mask Adjustment Range Multiplier
135 UNDERVOLTAGE TRIP
SELECTION 0 / 1 0080 0000: Trip disabled (0)
0080: Trip (during run) (1)
136 UNDERVOLTAGE DETECT
TIME 0 / 1 FFFF 0000 03E8 (0.00 10.00) 0.01
137 LOW CURRENT DETECT
SELECTION 0 / 1 0008 0000: Trip disabled (0)
0008: Trip on detection (1)
138 LOW CURRENT DETECT
LEVEL 0 / 1 00FF 0000 0064 (0 100) 1
139 LOW CURRENT DETECTION
TIME 0 / 1 00FF 0000 00FF (0 255) 1
140 OUTPUT SHORT-CIRCUIT
DETECTION SELECT 0 / 1 0003 0000: S t andard m otor (0)
0001: High-speed motor (1)
0002: Positioning use (standard
motor) (2)
0003: Positioning use (high-speed
motor) (3)
141 OVERTORQUE TRIP
SELECTION 0 / 1 0040 0000: Trip disabled (0)
0040: Trip enabled (1)
142 OVERTORQUE TRIP LEVEL 0 / 1 00FF 0000 00C8 (0 200) 1
143 FAULT TRIP EEPROM
SAVE ENABLE 0 / 1 0002 0000: Data cleared when powered
OFF (0)
0002: Data retained when powered
OFF (1)
144 COOLING FAN CONTROL
SELECTION 0 / 1 0004 0000: Automatic (temperature
detection) (0)
0004: Always ON (1)
145 CUMULATIVE RUN TIMER
ALARM SETTING 0 / 1 FFFF 0000 C34B (0.00 999.90) 0.02