50
Register Function / Title Bank Mask Adjustment Range Multiplier
211 TOSLINE-S20 COMM
ERROR MODE 1 0002 0000: Data cleared (0)
0002: Data retained (1)
1
212 TOSLINE-S20 COMM
OPTION RESET 1 0004 0000: No effect (0)
0004: Reset (1)
1
213 RS485/12-BIT BINARY
BIAS,GAIN 0 / 1 0020 0000: OFF (0)
0020: ON (1)
214 1
RS485/12-BIT
BINARY POINT #1 0 / 1 00FF 0000 0064 (0 100) 1
215 RS485/12-BIT
BINARY PT. #1
FREQ
0 / 1 FFFF 0000 Fmax (0 Fmax) 0.01
216 RS485/12-BIT
BINARY POINT #2 0 / 1 00FF 0000 0064 (0 100) 1
217 RS485/12-BIT
BINARY PT. #2
FREQ
0 / 1 FFFF 0000 Fmax (0 Fmax) 0.01
11.2.1111.2.1111.2.1111.2.11 GROUP:AM/FM TERMINAL ADJUSTMENT PARAMSGROUP:AM/FM TERMINAL ADJUSTMENT PARAMSGROUP:AM/FM TERMINAL ADJUSTMENT PARAMSGROUP:AM/FM TERMINAL ADJUSTMENT PARAMS
Register Function / Title Bank Mask Adjustment Range Multiplier
218 FM TERMINAL FUNCTION
SELECTION 0 / 1 FFFF 1194: Pre-c omp ref. frequency (0)
6686: Post-comp output freq. (1)
1500: Frequency setting (2)
2576: Output current (3)
2689: DC voltage (4)
5668: Output voltage (5)
3684: Torque current (6)
2688: Excitation current (7)
7506: PID feedback value (8)
0584: Motor overload ratio (9)
0586: Inverter overload ratio (10)
0588: DBR overload ratio (11)
835C: Input power (12)
835E: Output power (13)
A000: Fixed output (14)
2304: Peak output current (15)
8302: Peak input voltage (16)
219 FREQUENCY METER
ADJUSTMENT 0 / 1 FFFF 0000 FFFF 1
21A AM TERMINAL FUNCTION
SELECTION 0 / 1 FFFF Same as FM TERMINAL FUNCTION
SELECTION
21B CURRENT METER
ADJUSTMENT 0 / 1 FFFF 0000 FFFF 1