Toshiba G9000 manual Bypass

Models: G9000

1 17
Download 17 pages 22.24 Kb
Page 11
Image 11

Guide Specification – 3-Phase Static Uninterruptible Power Supply

5.3.5Overload Capacity:

The Inverter output shall be capable of providing an overload current of 125% for 2 min. and 150% for 1 min. A message on the control panel shall indicate this condition. If the time limit associated with the overload condition expires, or the overload is in excess of the set current limit, the load power shall transfer to the bypass source without interruption.

5.4Static Bypass Circuit:

5.4.1General:

An integral static bypass circuit shall be provided to supply an alternate source of power to the critical load in the event the inverter cannot supply rated output power. The bypass circuit shall be capable of supplying the UPS rated load current and accommodate fault clearing.

The 100% duty rated static bypass panel shall be composed of a thyristor switch with a wrap-around contactor. The thyristor switch shall be a high-speed transfer device. The wrap-around contactor shall be electrically connected in parallel to the thyristor switch and shall, at the same time as the thyristor switch, be energized and, upon closure, maintain the bypass source to the load to improve the efficiency and reliability of the system. The thyristor switch shall only be utilized for the time needed to energize the contactor closure.

The UPS system logic shall employ sensing which shall cause the thyristor switch to energize and provide an uninterrupted transfer of the load to the bypass source when any of the following limitations are exceeded:

Inverter output undervoltage or overvoltage.

Overloads exceeding 125% for 2 min., or 150% for 1 min. DC circuit undervoltage or overvoltage.

Final discharge voltage of system battery is reached and the bypass source is present, available, and within tolerance range

Transferring the output from the inverter to the bypass source and vice versa shall be performed by pressing “START/STOP” icon on the touchscreen display.

Operating Mode

Transfer mode

Transfer Type

Synchronized Unsynchronized

Automatic

Inverter to Bypass

Uninterrupted

Interrupted

(Overload, Internal Fault)

 

 

 

“BYPASS”

Inverter to Bypass

Uninterrupted

Interrupted

switch operated

(forced transfer)

 

 

Automatic

Bypass to Inverter

Uninterrupted

Transfer inhibited

(Auto-Retransfer Mode)

 

 

 

“UPS”

Bypass to Inverter

Uninterrupted

Transfer inhibited

switch operated

 

 

 

11

Page 11
Image 11
Toshiba G9000 manual Bypass