Guide Specification – 3-Phase Static Uninterruptible Power Supply

3.2.3 Clearances for installation

 

Ceiling Level

: 20” minimum from top of UPS to ceiling

Front

: 40” minimum for maintenance

 

(Local and regional codes may apply)

Bottom

: Knockouts for power cable access

Rear

: Zero clearance required

Sides

: Zero clearance if using bottom cable access

 

(Standard knockouts for left/right side

 

cable access )

Base

: Channel mounted

4SYSTEM PARAMETERS

4.1UPS Requirements:

4.1.1 General Requirements:

 

 

Rated Output Capacity

: 80/100/160/225 kVA

 

(72/90/144/202.5 kW)

AC/DC Rectifier Type

: AC/DC multi-level IGBT Rectifier

DC/AC Inverter Type

:DC/AC multi-level IGBT Inverter

 

Inverter

 

External Dimensions

(W) (D)

(H)*

80 kVA

: 27.6”x 32.8”x 78.7 (80.6)”

100 kVA

: 27.6”x 32.8”x 78.7 (80.6)”

160 kVA

: 35.4”x 32.8”x 78.7 (80.6)”

225 kVA

: 35.4”x 32.8”x 78.7 (80.6)”

 

* Unit height with fan assembly installed

Weight

 

 

80 kVA

: 855 lbs

 

100 kVA

: 855 lbs

 

160 kVA

: 1160 lbs

 

225 kVA

: 1230 lbs

 

Power Cable Access

: Bottom, Sides, Top Entry with optional

 

side cabinet

 

Paint Color

: Black (Munsell N1.5)

4.1.2 AC Input:

 

 

Configuration

: 3-Phase/3-Wire + Ground

Rated Voltage

: 480V

 

Voltage Variation

: +15% to –20%

 

Rated Frequency

: 60Hz

 

Frequency Variation

: +/-10%

 

Input Power Factor

: Greater than 0.99 lagging at 25%-115% load