Guide Specification – 3-Phase Static Uninterruptible Power Supply

9.1.2HTTP Familiarity

The RemotEye II shall provide a HTTP interface for the UPS to allow easy access of the UPS information from any machine with a web browser. At any time, a network workstation or management station shall be able to open a RemotEye II website. RemotEye II website shall enable the UPS system information to be configured and monitored remotely. RemotEye II shall provide access to 3 java applets for monitoring, event logging, and trend analysis.

9.1.3Shutdown Capability

The RemotEye II application software shall allow RemotEye II to remotely notify and shutdown selected network servers.

Network Adapter/External Hardware

AMD 188ES-20MHz

512kB SRAM: 512kB Flash

Two asynchronous serial ports

10 BaseT RJ-45 connector

Toshiba UPS communication protocol

SNMP over UDP/IP : HTTP over TCP/IP:ARP, RARP, TFTP and

ICMP

MIB_II : Toshiba v1.2_MIB :JEM MIB : RFC 1628

Traffic LED for network : Status LED for status : Power LED for

Power

2 digit (default setting is Switches 1 and 2 off)

Temperature Range: 0 – 40 C

Relative Humidity: 10 – 80 %

Power Requirements: 12 VDC ungrounded

2.0 Watts Maximum

Dimensions: 5.28”(134mm) x 3.40”(86mm) x 1.10”(27mm) (LxWxH)

Weight: 0.38lbs(170g)

Certifications: FCC class A, UL, CUL, CE

9.2Remote Status Alarm Panel (RSAP)

The manufacturer shall optionally provide a RSAP that shall provide a wall-mounted LED mimic display for UPS status events of:

Input ON Bypass ON Inverter ON

Low Battery, AC Fail New alarm annunciation

Battery backup for the RSAP monitor.