Guide Specification – 3-Phase Static Uninterruptible Power Supply

5.5.4Mimic Panel

A one-line diagram of the system shall be displayed on the touch panel display panel to provide a visual status of contactors within UPS. The panel shall display the followings:

AC Input, DC Input Rectifier in Operation Inverter in Operation UPS/Bypass supply

Battery Operating Condition (float charge/discharge) Fault, Warning

Operation Guidance (LCD Display) Fault Guidance (LCD Display)

5.5.5Isolated Control Signals

Normally Open isolated contact signal outputs for remote use will be furnished for the following operating status indications:

Summary Alarm Load on Bypass Load on Inverter Battery Operation Rectifier Operation Battery Low Voltage Overload

Total alarm

Output Contactor Closed

Contact rating:

Output: 1 A @ 30 VDC.

Input: 24 VDC

UPS module accepts remote switches to initiate the following remote operations. These contacts shall be field supplied):

Remote Start Remote Stop

Battery Temperature High Power Demand Emergency Power Off (EPO)

Contact rating:

Input: 24 VDC

The contact signal inputs and outputs shall be wired to a terminal block located inside the UPS.