Guide Specification –
5.5.4Mimic Panel
A
AC Input, DC Input Rectifier in Operation Inverter in Operation UPS/Bypass supply
Battery Operating Condition (float charge/discharge) Fault, Warning
Operation Guidance (LCD Display) Fault Guidance (LCD Display)
5.5.5Isolated Control Signals
Normally Open isolated contact signal outputs for remote use will be furnished for the following operating status indications:
Summary Alarm Load on Bypass Load on Inverter Battery Operation Rectifier Operation Battery Low Voltage Overload
Total alarm
Output Contactor Closed
Contact rating:
Output: 1 A @ 30 VDC.
Input: 24 VDC
UPS module accepts remote switches to initiate the following remote operations. These contacts shall be field supplied):
Remote Start Remote Stop
Battery Temperature High Power Demand Emergency Power Off (EPO)
Contact rating:
Input: 24 VDC
The contact signal inputs and outputs shall be wired to a terminal block located inside the UPS.