Guide Specification – 3-Phase Static Uninterruptible Power Supply

Current THD

: <3% THD at 60%–100% load

 

<6% THD at 25%–59% load

 

(No input harmonic filter required)

4.1.3Charging Function: DC Nominal Voltage AC Ripple on DC Bus DC Voltage Range

DC Float Charging Voltage Maximum charging current:

80 kVA

100 kVA

160 kVA

225 kVA

AC Ripple on DC Charging Circuit 80 kVA

100 kVA

160 kVA

225 kVA

4.1.4Bypass Input:

Configuration

Rated Voltage

Input voltage synchronous range Rated frequency

Frequency Variation Frequency synchronous range Bypass overload capacity

4.1.5AC Output: Configuration Rated Capacity Rated Voltage Efficiency at % Full Load

80 kVA

100 kVA

150 kVA

225 kVA

Voltage Regulation

Voltage Adjustment Range

Rated Frequency

Frequency Regulation

Frequency Synchronous Range

Rated Load Power Factor

Overload Capacity

:480 V

:< 0.2% of DC Voltage

:400 V to 545 V

:545 V

:20 A

:25 A

:40 A

:56 A

:

:0.23%

:0.23%

:0.23%

:0.29%

:3-Phase/3-Wire + Ground

:480 V

:+/-10%

:60 Hz

:+/-5%

:+/-1.0 Hz

:1000% for 1 cycle

:3-Phase/3-Wire + Ground

:80/100/160/225 kVA (72/90/144/202.5 kW)

:480 V

:20% 40% 60% 80% 100%

92.5% 95.6% 95.6% 95.6% 95.6%

92.5% 95.6% 95.6% 95.6% 95.6%

94.6% 96.2% 96.2% 96.2% 96.5%

94.7% 96.2% 96.2% 96.2% 96.5%

:+/-1% (0-100% Unbalanced Load)

:+/-1% (0-100% Balanced Load)

:+/-3%

:60 Hz

:+/-0.01% (Free-Running Mode)

:+/-0.5 Hz or +/-1.0 Hz (Selectable)

:0.9 PF lagging

:125% for 2 min., 150% for 1 min.

8