60
CN300 : Motor coil winding
CN301 : Motor position detection
CN301, CN303 : Motor coil winding
CN300, CN302 : Motor position detection
SP562AT-E
Normal fan motor
(Control or CDB P.C. board) Defective fan motor
(Control P.C. board or CDB P.C. board)
NO
NO
NO
YES
YES
YES
YES
CN301, CN303CN300
Are connections of CN301 and CN300
of P.C. board correct?
Does the fan rotate without trouble
when handling the fan with hands under condition
of removing CN301 and CN300 from P.C. board?
The status that there is
5k to 20kW resistance values between
1
(Yellow lead) and
4
(Pink lead) of
motor position detection of
connector (CN300) is normal.
The status that the resistance values
between leads below are 50 to 80
for 40 motor (ICF-140-40) and 25 to 55
for 60 motor (ICF-140-60-1) is normal.
Between
1
(Red lead) and
2
(White lead)
Between
2
(White lead) and
3
(Black lead)
Between
3
(Black lead) and
1
(Red lead)
of motor winding of connector (CN301)

[P22 error]

Objective P.C. board
Fan motor winding
Motor position detection
Single phase
RAV-SM562AT-E, SM563AT-E RAV-SP562AT-E
RAV-SP404AT-E, SP454AT-E
Control P.C. board CDB P.C. board
CN300 CN301
CN301 CN300

NOTE :

However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.
When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.