8
<Triple type>
Indoor unit 1 RAV-SM562MUT-E
Model Indoor unit 2 RAV-SM562MUT-E
Indoor unit 3 RAV-SM562MUT-E
Outdoor unit RAV-SM1603AT-E
Cooling capacity (kW) 14.0
Heating capacity (kW) 16.0
Indoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 23.88 21.89
Power consumption (kW) 4.99
Cooling Power factor (%) 95
EER 2.81
Electrical Energy efficiency class C
characteristics Running current (A) 22.44 20.57
Power consumption (kW) 4.69
Heating Power factor (%) 95
COP 3.41
Energy efficiency class B
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 13.3 / 11.2 / 9.1
Motor (W) 60
Sound pressure level H/M/L (dBA) 43 / 39 / 34
Sound power level H/M/L (dBA) 58 / 54 / 49
Outdoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5
Min. length (m) 5 .0
Outer dimension Max. total length (m) 50
Height Outdoor lower (m) 30
difference Outdoor higher (m) 30
Fan Propeller fan
Fan unit Standard air flow volume (m³/min.) 103
Motor (W) 100 + 100
Gas side Main (mm) 15.9
Connecting pipe Sub (mm) 12.7
Liquid side Main (mm) 9.5
Sub (mm) 6.4
Sound pressure level Cooling/Heating (dBA) 51 / 53
Sound power level Cooling/Heating (dBA) 68 / 70
: IEC standard