FILE NO. SVM-06012

 

 

 

Table 9-2-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation of diagnostic function

 

 

 

Judgement and action

 

 

 

 

 

 

 

 

 

Check code

 

Symptom

Unit status

Condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter over-current protective circuit

All stop

Displayed when

1.

Inverter immediately stops even if restarted.

 

 

operates.

 

error is detected

 

Compressor rare short

 

 

(For a short time)

 

 

2.

Check IPDU.

 

 

 

 

 

 

 

Cabling error

 

 

 

 

 

 

 

 

 

Error on current detection circuit

All stop

Displayed when

1.

Compressor immediately stops even if restarted.

 

 

Current value is high at AC side even

 

error is detected

 

: Check IPDU.

 

 

while compressor stops.

 

 

2.

Phase-missing operation of power supply

 

 

Phase of power supply is missed.

 

 

 

Check power voltage of R, S, T.

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or short of

All stop

Displayed when

1.

Check outdoor temp sensor (TE, TS).

 

 

outdoor temp sensor

 

error is detected

2.

Check CDB.

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or short of

All stop

Displayed when

1.

Check outdoor temp sensor (TD).

 

 

outdoor temp sensor

 

error is detected

2.

Check CDB.

 

 

 

 

 

 

 

 

 

Compressor drive output error

All stop

Displayed when

1.

Abnormal overload operation of refrigerating

 

 

Tin thermistor temp, Tin error

 

error is detected

 

cycle

 

 

 

(IPDU heat sink temp. is high.)

 

 

2.

Loosening of screws and contact error of IPDU

 

 

Communication error between IPDU

 

 

 

and heat sink

 

 

Connector coming-off between CDB and

 

 

3.

Cooling error of heat sink

 

 

 

IPDU

 

 

4.

Check cabling of CDB and IPDU.

 

 

 

 

 

 

 

 

 

Compressor does not rotate. (Over-current

All stop

Displayed when

1.

Compressor error (Compressor lock, etc.)

 

 

protective circuit works when constant time

 

error is detected

 

: Replace compressor.

 

 

passed after activation of compressor.)

 

 

2.

Cabling trouble of compressor (Phase missing)

 

 

 

 

 

 

 

 

 

Discharge temp error

All stop

Displayed when

1.

Check refrigerating cycle. (Gas leak)

 

 

Discharge temp over specified value was

 

error is detected

2.

Error of electron control valve

 

 

 

detected.

 

 

3.

Check pipe sensor (TD).

 

 

 

 

 

 

 

 

 

Compressor breakdown

All stop

Displayed when

1.

Check power voltage. (AC200V±20V)

 

 

Operation frequency lowered and stops

 

error is detected

2.

Overload operation of refrigerating cycle

 

 

 

though operation had started.

 

 

3.

Check current detection circuit at AC side.

 

 

 

 

 

 

 

 

 

High-voltage protection error by TE sensor

All stop

Displayed when

1.

Overload operation of refrigerating cycle

 

 

TE temp over specified value was

 

error is detected

2.

Check outdoor temp sensor (TE).

 

 

 

detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC outdoor fan motor error

All stop

Displayed when

1.

Position detection error

 

 

IDC operation or lock was detected by

 

error is detected

2.

Over-current protection circuit operation of

 

 

 

DC outdoor fan driving.

 

 

 

outdoor fan drive unit

 

 

 

 

 

 

 

Check CDB.

 

 

 

 

 

 

 

Refer to Judgment of outdoor fan.

 

 

 

 

 

 

 

 

 

Error on IPDU position detection circuit

All stop

Displayed when

1.

Position detection circuit operates even if driving

 

 

 

 

 

error is detected

 

by removing 3P connector of compressor.

 

 

 

 

 

 

 

Replace IPDU.

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or short of

Operation

Displayed when

1.

Check outdoor temp sensor (TO).

 

 

outdoor temp sensor

continues.

error is detected

2.

Check P.C. board.

 

 

 

 

 

 

 

 

 

 