Outdoor Unit | Installation Manual |
Barriers in front and back of unit
Open above and to the right and left of the unit.
The height of an barrier in both the front and rear of the unit, should be lower than the height of the outdoor unit.
▼Standard installation
1. Single unit installation
39.4” (1000) 5.9” (150) or more or more
2.Multiple unit installation
a. Intake and supply parallel
Installation of Outdoor Unit
•Before installation, check the strength and horizontal of the base so that abnormal sounds do not emanate.
•According to the following base diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: 3/8” (M10) x 4 pairs)
3.5” (90) | 3.5” (90) | |
|
| 23.6” (600) |
|
| 4.3” (108) |
(330) | (306) | 2.4” (60) |
13.0” | 12.1” | Ø1.0” (25) |
|
| Drain hole |
1)Field fabricate a snow or an ice stand for the unit using the above dimension.
2)Place snow or ice stand on a foundation/pad and secure it to the foundation/pad and secure it to the foundation/pad by anchor bolts.
11.8” (300) or more
11.8” (300) or more
39.4” (1000) 7.9” (200) or more or more
NOTE
When the outdoor unit is anchored directly on the foundation/pad (cooling only protrude a minimum of 0.6” (15 mm)).
0.6” (15 mm) or less
b.Intake and supply in line
Open above and to the right and left of the unit. The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit.
▼Standard installation
39.4” | 11.8” | 59.1” | 78.7” | 7.9” |
(1000) | (300) or | (1500) | (2000) | (200) |
or more | more | or more | or more | or more |
EN
– 10 – |