5 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER

Outdoor Unit

Installation Manual

5 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER

„Required Tools/Equipment and Precautions for Use CAUTION

New Refrigerant Air Conditioner Installation

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.

R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigerant oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerant oil does not enter the new type refrigerant R410A air conditioner cycle.

To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter.

„Required Tools/Equipment and Precautions for Use

Prepare the tools and equipment listed in the following table before starting the installation work. – 7 –: R410A exclusive

Manual background : Generic

Tools/equipment

Use

 

Manifold gauge*

Vacuuming/charging refrigerant

 

Charging hose

and operation check

 

 

 

Gas leak detector

Gas leak check

 

Vacuum pump with backflow

Vacuum drying

 

prevention function

 

 

 

Flare tool

Flare machining of pipes

Usable if dimensions are adjusted.

Bender

Bending pipes

 

Refrigerant recovery equipment

Refrigerant recovery

 

Torque wrench

Tightening flare nuts

Ø1/4” (6.4 mm) and Ø1/2” (12.7 mm)

Pipe cutter

Cutting pipes

 

Brazing torch and nitrogen

Braze pipes

 

cylinder

 

 

 

Refrigerant charging scales

Charging refrigerant

 

4 mm hexagon wrench

Opening liquid valve

 

7-EN

– 7 –

Page 8
Image 8
Toshiba RAV-SP180AT2-UL Installation Of New Refrigerant Air Conditioner, „Required Tools/Equipment and Precautions for Use