Outdoor Unit

Installation Manual

3 SYSTEM REQUIREMENTS

„Piping (Field supplied)

Minimum refrigerant line length between the outdoor unit and indoor unit is 16.5” (5 m)

Maximum pipe lengths

Allowable

Height difference

Number of

pipe length

(Indoor-outdoor H)

bent portions

(ft (m))

(ft (m))

 

 

 

 

 

Total length

Indoor unit:

Outdoor unit:

 

L

Upper

Lower

10 or less

164’1” (50)

98’5” (30)

98’5” (30)

 

 

 

 

 

Figure of Single

Indoor Unit

Refrigerant charge

Length of refrigerant

Additional refrigerant

pipe connected to

indoor/outdoor unit

 

16’5” - 65’7”

None

(5 - 20 m)

 

*65’7” - 164’1”

Add 0.22 oz/ft (20 g/m) of

refrigerant for piping that exceeds

(20 - 50 m)

65’7” (20 m) up to 164’1” (50 m).

 

 

 

*Caution during addition of refrigerant

Max. amount of additional refrigerant is 1.8 lbs (800 g).

Charge the refrigerant accurately. Overcharging may cause serious trouble with the compressor.

*Minimum refrigerant pipe is 16’5”(5 m).

This may cause a malfunction of the compressor or other devices.

Outdoor Unit

H

L

Refrigerant sizes

Liquid side

Gas side

 

 

 

 

Outer

Thickness

Outer

Thickness

diameter

diameter

 

 

Ø1/4”

0.03”

Ø1/2”

0.03”

(6.4 mm)

(0.8 mm)

(12.7 mm)

(0.8 mm)

Flare nuts and flaring

The flare nuts and flaring are different from those for the conventional refrigerant.

Use the flare nuts supplied with the air conditioner or those for R410A.

Before performing flaring, carefully read

“REFRIGERANT PIPING”

Insulation

Both lines need to be insulated. Use a minimum 0.4” (10 mm) wall thickness.

Metering Device is an electronic EXV (PMV) in outdoor unit.

„Connecting power and control cables (Field supplied)

The main power is supplied to the outdoor unit. The field supplied connecting cables from the outdoor unit to the indoor unit consist for 4 wires and provides the power for the indoor unit as well as the communication signal between the outdoor and indoor unit.

Consult local building codes, NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.

The following are the electrical requirements.

Model RAV-

 

SP180

 

 

 

 

 

 

 

Power supply

 

208/230 V~, 60 Hz

 

 

 

 

 

 

 

MCA

 

17 A

 

 

 

 

 

 

 

MOCP (MAX Fuse/CB)

 

30 A

 

 

 

 

 

 

 

Breaker

 

20 A

 

 

 

 

 

 

 

 

 

Maximum 65’7” (20 m)

 

 

Power wire

 

2 x AWG12

 

 

 

 

Ground : AWG14

 

 

System

 

4 x AWG12

 

 

interconnection wires

 

 

 

 

 

 

 

MCA = Minimum Circuit Amps

 

 

 

 

 

 

MOCP =Maximum Over Protection Device Amps.

EN

 

 

 

 

 

 

 

 

 

– 4 –

4-EN

Page 5
Image 5
Toshiba RAV-SP180AT2-UL installation manual System Requirements, „ Piping Field supplied

RAV-SP180AT2-UL specifications

The Toshiba RAV-SP180AT2-UL is an innovative ducted air conditioning unit designed to deliver exceptional cooling and heating capabilities for both residential and commercial applications. Known for its efficiency and performance, this model integrates advanced technology that ensures optimal indoor climate control.

One of the primary features of the RAV-SP180AT2-UL is its energy efficiency. It operates with a high Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER) ratings, allowing it to consume less electricity while providing maximum comfort. This efficiency not only contributes to lowering energy bills but also promotes environmentally friendly practices by reducing carbon emissions.

The air conditioning unit is equipped with Toshiba’s advanced inverter technology. This technology allows for precise temperature control and significant energy savings by continuously adjusting the compressor speed based on the desired temperature. With this capability, the system can operate quietly and maintain a stable climate, avoiding the sharp temperature fluctuations characteristic of traditional fixed-speed units.

Another significant feature of the RAV-SP180AT2-UL is its compact design, making it suitable for installation in various settings, including small apartments and larger commercial spaces. Its ducted system enables seamless air distribution, reducing visible components and maintaining the aesthetic of the interior space.

The unit also incorporates innovative filtration systems that improve indoor air quality. With advanced air purifying filters, it effectively minimizes allergens, dust, and pollutants, ensuring that the air circulated in the space is clean and healthy.

In terms of control, the RAV-SP180AT2-UL is compatible with a range of smart control options. Users can manage settings remotely via applications or programmable timers, allowing for convenience and the possibility of scheduling cooling and heating cycles according to personal routines.

Overall, the Toshiba RAV-SP180AT2-UL combines efficiency, compact design, and advanced technology, making it a strong contender in the ducted air conditioning market. Its ability to provide comfortable air conditioning solutions while being mindful of energy consumption is a testament to Toshiba's commitment to innovation in climate control technology.