7 ELECTRICAL CONNECTIONS

Outdoor Unit

Installation Manual

7 ELECTRICAL CONNECTIONS

„Field wiring WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Before performing service or maintenance, be sure main power switch is turned OFF.

– 14 – CAUTION

All wiring and connections must comply with NEC, CEC, local codes.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage or improper operation.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

Wrong wiring may cause a burn-out of some electrical parts.

Do not damage or scratch the conductive core or inner insulator of the power and inter-connecting wires when peeling them.

Electric parts box

Electric control box

„Field wiring

The dashed lines show field wiring.

 

(Field power

(System

 

 

 

supply)

interconnection wires)

Input

L1

L1

L1

 

power

L2

L2

L2

 

208/230 V~,

Remote

 

S

S

60 Hz

 

controller

circuit breaker

Outdoor unit

Indoor unit

 

ground

System interconnection wire size must be AWG12.

Breaker must have a capacity specified in the following table.

All wiring must comply with local electric codes and NEC (National Electric Code) or CEC (Canadian Electric Code).

Model RAV-

SP240

 

 

Power supply

208/230 V, 60 Hz

 

 

MCA

24 A

 

 

MOCP (MAX Fuse/CB)

40 A

 

 

Breaker

25 A

 

 

System interconnection wires

AWG12

 

 

MCA = Minimum Circuit Amps

MOCP =Maximum Over Protection Device Amps.

Connect the system interconnection wires (indoor to outdoor) to the identical terminal numbers on the terminal block of each unit.

Incorrect connection may cause a failure.

Manual background Field wiring terminal blocks

Valve mounting bracket

Front PipePipecoverco

Front panel

Front pane

Conduit connection Conduit connection holes

holes

PipingPipingknockoutknockout

1.With the front panel removed the electrical control box is exposed at the top right corner of the unit.

2.Terminate the field wiring conduit (if used) at the conduit connection holes provided.

3.Route the field power wires and the system interconnection wires as shown on the following pages. Terminate the wires at field wiring terminal blocks located immediately below the electrical control box.