4.5. Examples of the use of communication commands

Here are some examples of the use of communication commands provided for the VF-AS1 series of inverters.

Inverter numbers and checksum used in ASCII mode are omitted from these examples.

„Examples of communication

-To run the motor in forward direction with the frequency set to 60 Hz from the computer <ASCII mode>

Computer Inverter

Inverter Computer

(PFA011770)CR

(PFA011770)CR …Set the operation frequency to 60 Hz.

 

 

 

(60 / 0.01 Hz = 6000 = 1770H)

(PFA00C400)CR

(PFA00C400)CR …Set to “forward run” with commands and frequency

 

 

 

instruction from the computer enabled.

<Binary mode>

 

 

Computer Inverter

Inverter Computer

2F

50 FA 01 17 70 01

2F

50 FA 01 17 70 01

2F

50 FA 00 C4 00 3D

2F

50 FA 00 C4 00 3D

-To monitor the output frequency (during 60 Hz operation) <ASCII mode>

Computer Inverter

Inverter Computer

(RFD00)CR

(RFD001770)CR …Set the operation frequency to 60 Hz.

 

(600.01Hz=6000=1770H)

<Binary mode>

 

Computer Inverter

Inverter Computer

2F 52 FD 00 7E

2F 52 FD 00 17 70 05

-To monitor the status of the inverter <ASCII mode>

Computer Inverter

Inverter Computer

(RFD01)CR

(rFD010003)CR

…For details on statuses, see 8.2 “Monitoring from

 

 

the computer.” (Stop status, FL output status, trip

 

 

status (r command))

<Binary mode>

 

 

Computer Inverter

Inverter Computer

2F 52 FD 01 7F

2F 72 FD 01 00 03 A2

- To check the trip code (when the inverter is tripped because of )

 

…For details on trip codes, see “Trip code monitor” in 8.2, “Monitoring

 

from the computer.” (18H = 24d “” trip status)

<ASCII mode>

 

Computer Inverter

Inverter Computer

(RFC90)CR

(rFC900018)CR

<Binary mode>

 

Computer Inverter

Inverter Computer

2F 52 FC 90 0D

2F 72 FC 90 00 18 45