Toshiba VF-AS1 Series „ Inverter operating command mode status FD45, FE45, Preset speed operation

Models: RS485 VF-AS1 Series

1 73
Download 73 pages 28.99 Kb
Page 55
Image 55

E6581315

„Inverter operating command mode status (FD45, FE45)

The monitor of the command mode that the present condition is enabled

Command mode status (current status): “Communication Number FD45”

Command mode status (status immediately before the occurrence of a trip): “Communication Num- ber

Data

Enabled command

0

Terminal input enabled

1

Operation panel input enabled

2

Operation panel RS485 (2-wire) communication input

3

Internal RS485 (4-wire) communication input

4

Communication option input

„Inverter operating frequency mode status (FD46, FE46)

The monitor of the frequency command mode that the present condition is enabled

Note that Preset speed operation frequencies is given the priority independent of the frequency mode, in which case this monitor will be disabled, in case Preset speed operation frequencies is selected.

Frequncy mode status (current status): Communication Number FD46

Frequncy mode status (status immediately before the occurrence of a trip): Communication Number FE46

Data

Enabled frequency

1

VI/II input

2

RR/S4 input

3

RX input

4

Operation panel input enabled

5

Operation panel RS485 (2-wire) communication input

6

Internal RS485 (4-wire) communication input

7

Communication option input

8

Optional AI1

9

Optional AI2

10

UP/DOWN frequency

11

RP pulse input

12

High-speed pulse input

13

Binary/BCD input

255

Preset speed operation

54

Page 55
Image 55