Toshiba RS485, VF-AS1 Series Appendix 3 Compatibility with the communication function, VF-A7

Models: RS485 VF-AS1 Series

1 73
Download 73 pages 28.99 Kb
Page 70
Image 70

E6581315

Appendix 3 Compatibility with the communication function

of the VF-A7

To provide consistency in communication procedures, the communication function of the VF-AS1 series of inverters has been designed based on the protocols used for the Toshiba VF-A7 series of inverters. With regard to compatibility, however, VF-A7 users should check the items described be- low before using the communication function of their inverters.

„To VF-AS1 inverter users:

Some parameters of the VF-A7 are different from those of the VF-AS1 in function or adjustment range (upper and lower limits), even though they have the same title or the same communication number. So, when accessing a parameter, consult the VF- A7 inverter’s instruction manual to see if the parameter is identical to the corresponding parameter of the VF-AS1. If the parameter differs, modify the computer program to suit your inverter. To avoid hazards, never copy parameters from one model of inverter to another.

„Comparison of communication-related items

The table below gives a comparison of communication-related items to be kept in mind when re- placing VF-A7 inverters with VF-AS1 inverters or when connecting VF-A7 inverters and VF-AS1 in- verters to the same network. It does not cover any items common to the VF-A7 and VF-AS1 series of inverters.

Model

VF-A7 series

VF-AS1 series

Reference

Item

 

 

 

 

 

 

 

32-bit mode

For some parameters, including accel-

32-bit mode is not available. For all

Refer to

 

eration/deceleration time parameters,

parameters, access is made in 16-bit

Section 9.

 

data communication are carried out in

mode.

 

 

32-bit mode.

 

 

Handling of negative

Access is made in 32-bit mode.

Access is made in 16-bit mode. To

data specified with pa-

 

see if the value specified with a

 

rameters

 

parameter is signed or not, check the

 

 

 

adjustment range of the parameter.

 

Division of a frame

A frame can be sent with it divided into

No frame can be divided into smaller

Refer to

 

smaller frames if all the frames can be

frames. Do not place an interval cor-

Section

 

sent within approx. 0.5 sec.

responding to less than 1.5 bytes of

3.1.

 

 

data between frames to be sent.

 

Communication time-

0.5 sec.

0.1 sec.

 

out period (guide)

 

 

 

Receipt information in

Even if there is receipt information in

A frame must always begin with a start

 

front of the start code

front of the start code of a frame re-

code, otherwise it will be rejected.

 

 

ceived, the frame is assumed to begin

 

 

 

with the start code.

 

 

Reset command

When an inverter receives a reset com-

When an inverter receives a reset

Refer to

 

mand, it sends back a response before it

command, it sends back no response.

Section

 

is reset.

 

8.1.

RS485 baud rate

1200 to 38400 bps

9600 to 38400 bps

Refer to

 

 

 

Section

 

 

 

7.1.

Notice

Do not use communication programs written for another series of inverters.

Even though parameters have the same title and the same communication number, they may be different in function. When using a parameter, always check its specifications in the instruction manual for your inverter. If the specifications of the parameter differ, modify the computer program to suit your inverter.

To avoid hazards, do not copy parameters from one model of inverter to another.

Even though parameters have the same titles and communication numbers, they may be different in function.

69

Page 70
Image 70
Toshiba RS485, VF-AS1 Series instruction manual Appendix 3 Compatibility with the communication function, VF-A7