5.Modbus Module Operation

5.Modbus Module Operation

5.1.Modbus Commands

When a MODBUS command is used, the Modbus module translates it to the corresponding T2 register access protocol.

 

MODBUS FUNCTION CODE

 

T2 COMMAND

 

 

 

 

01

Read Coil Status

DR

Read Device/Register

02

Read Input Status

DR

Read Device/Register

03

Read Holding Register

DR

Read Device/Register

04

Read Input Register

DR

Read Device/register

05

Force Single Coil

DW

Write Device Register

06

Force Single Register

DW

Write Device/Register

08

Loop Back Diagnostic test

**** Not Supported by EX10-MML11

15

Force Multiple Coils

DW

Write Device/register

16

Preset Multiple Registers

DW

Write Device/register

For more information on the Modbus protocol, please refer to the Modbus Protocol Reference Guide, see Additional References.