General
Data
Product Specifications
Model No. 1 |
| 2TWB3042A1 | 2TWB3048A1 | 2TWB3060A1 |
Electrical Data V/Ph/Hz 2 | 200/230/1/60 | 200/230/1/60 | 208/230/1/60 | |
Min Cir Ampacity |
| 21 | 25 | 32 |
Max Fuse Size (Amps) |
| 35 | 40 | 50 |
Compressor |
| CLIMATUFF® | CLIMATUFF® | CLIMATUFF® - SCROLL |
RL Amps - LR Amps |
| 15.4 - 93.5 | 18.6 - 93.4 | 25.0 - 148 |
Outdoor Fan FL Amps |
| 1.4 | 1.4 | 1.2 |
Fan HP |
| 1/6 | 1/5 | 1/5 |
Fan Dia (inches) |
| 27.6 | 27.6 | 27.6 |
Coil |
| Spine Fin™ | Spine Fin™ | Spine Fin™ |
Refrigerant | ||||
Line Size - (in.) O.D. Gas 3 | 7/8 | |||
Line Size - (in.) O.D. Liquid 3 | 3/8 | 3/8 | 3/8 | |
Dimensions H x W x D (Crated) | 46.4 x 35.1 x 38.7 | 46.4 x 35.1 x 38.7 | 46.4 x 35.1 x 38.7 | |
Weight - Shipping |
| 308 | 312 | 291 |
Weight - Net |
| 272 | 276 | 255 |
Start Components |
| YES | YES | NO |
Sound Enclosure |
| YES | YES | NO |
Compressor Sump Heat | YES | YES | YES | |
Optional Accessories: 4 |
|
|
| |
| TAYASCT501A | TAYASCT501A | TAYASCT501A | |
Evaporator Defrost Control A/C | AY28X084 | AY28X084 | AY28X084 | |
Rubber Isolator Kit |
| BAYISLT101 | BAYISLT101 | BAYISLT101 |
Snow | BAYLEGS002 | BAYLEGS002 | BAYLEGS002 | |
Snow | BAYLEGS003 | BAYLEGS003 | BAYLEGS003 | |
Extreme Condition | Mounting Kit | BAYECMT004 | BAYECMT004 | BAYECMT004 |
Refrigerant Lineset | 5 | TAYREFLN3* | TAYREFLN4* | TAYREFLN4* |
|
|
|
|
|
Accessory Description and Usage
Evaporator Defrost Control — SPST Temperature actu- ated switch that cycles the condenser off as indoor coil reaches
Rubber Isolators — 5 large rubber donuts to isolate condensing unit from transmitting energy into mounting frame or pad. Use on any application where sound transmis- sion needs to be minimized.
Hard Start kit — Start capacitor and relay to assist compressor motor startup. Use in areas with marginal power supply, on long linesets, low ambient conditions, etc.
Extreme Condition Mount Kit — Bracket kits to securely mount condensing unit to a frame or pad without removing any panels. Use in areas with high winds, or on commercial roof tops, etc.
AHRI Standard Capacity Rating Conditions
AHRI STANDARD 210/240 RATING CONDITIONS —
(A)Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil.
(B)High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil.
(C)Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil.
(D)Rated indoor airflow for heating is the same as for cooling.
AHRI STANDARD 270 RATING CONDITIONS — (Noise rating numbers are determined with the unit in cooling operation.) Standard Noise Rating number is at 95°F outdoor air.
SPLIT SYSTEM
5 |