Table PD-5. High Static Motor, Group 1

Performance

Hot Water

Data

Coils

 

 

 

 

 

 

Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (-1 C) T. All performance measured on high speed tap, zero ESP, and a throwaway filter.

Table PD-5. High Static Motor, Group 1

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

Unit

 

CFM

TMBH

 

GPM

WPD

 

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(L/s)

(kPa)

Watt

Watt

Watt

2

2H

287

(135)

17.9 (5.3)

0.16

1.19

(0.08)

6.0 (17.8)

145

145

145

 

3H

282

(133)

22.9 (6.7)

0.21

1.52

(0.10)

13.8 (41.2)

145

145

145

 

4H

260

(123)

23.9 (7.0)

0.22

1.59

(0.10)

3.8 (11.5)

145

145

145

3

2H

365

(172)

23.0 (6.7)

0.21

1.53

(0.10)

10.3 (30.8)

140

140

140

 

3H

343

(162)

27.3 (8.0)

0.25

1.82

(0.11)

4.3 (12.8)

145

140

135

 

4H

318

(150)

29.7 (8.7)

0.27

1.98

(0.12)

6.2 (18.6)

145

140

135

4

2H

396

(187)

26.0 (7.6)

0.24

1.73

(0.11)

3.3 (9.8)

170

180

170

 

3H

484

(228)

38.6

(11.3)

0.35

2.57

(0.16)

9.1 (27.0)

210

210

210

 

4H

453

(214)

42.2

(12.4)

0.38

2.81

(0.18)

13.4

(39.9)

210

210

210

6

2H

668

(315)

43.1

(12.6)

0.39

2.87

(0.18)

9.9 (29.5)

245

240

240

 

3H

780

(368)

59.5

(17.4)

0.54

3.96

(0.25)

5.9 (17.7)

320

320

320

 

4H

725

(342)

65.6

(19.2)

0.60

4.37

(0.28)

8.2 (24.6)

320

320

320

8

2H

907

(428)

55.7

(16.3)

0.51

3.71

(0.23)

4.7 (14.2)

320

320

320

 

3H

886

(418)

71.2

(20.9)

0.65

4.74

(0.30)

9.1 (27.1)

320

320

320

 

4H

835

(394)

78.3

(22.9)

0.71

5.22

(0.33)

12.7

(37.8)

320

320

320

10

2H

1117 (527)

70.8

(20.7)

0.65

4.71

(0.30)

8.1 (24.1)

415

420

410

 

3H

1230 (580)

97.6

(28.6)

0.89

6.50

(0.41)

18.1

(54.0)

530

530

530

 

4H

1152 (544)

107.1

(31.4)

0.97

7.13

(0.45)

25.3

(75.6)

530

530

530

12

2H

1270 (600)

82.2

(24.1)

0.75

5.48

(0.35)

11.4

(34.0)

490

500

490

 

3H

1350 (637)

108.0

(31.6)

0.98

7.19

(0.45)

14.5

(43.2)

530

530

530

 

4H

1274 (601)

120.0

(35.2)

1.09

7.83

(0.51)

10.5

(31.4)

530

530

530

Table PD-6. High Static Motor, Group 2

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

Unit

 

CFM

TMBH

 

GPM

WPD

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(L/s)

(kPa)

Watt

Watt

Watt

2

2H

256

(121)

16.6 (4.9)

0.15

1.11

(0.07)

5.2 (15.5)

145

145

145

 

3H

250

(118)

20.9 (6.1)

0.19

1.39

(0.09)

11.8 (35.3)

145

145

145

 

4H

234

(111)

22.0 (6.5)

0.20

1.47

(0.09)

3.3 (9.9)

145

145

145

3

2H

330

(156)

21.5 (6.3)

0.20

1.43

(0.09)

9.2 (27.4)

140

140

140

 

3H

309

(146)

25.3 (7.4)

0.23

1.68

(0.11)

3.7 (11.1)

145

140

135

 

4H

290

(137)

27.6 (8.1)

0.25

1.84

(0.12)

5.4 (16.3)

145

140

135

4

2H

367

(173)

24.6 (7.2)

0.22

1.64

(0.10)

3.0 (8.9)

170

180

170

 

3H

440

(208)

36.0

(10.5)

0.33

2.40

(0.15)

8.0 (23.8)

210

210

210

 

4H

416

(196)

39.5

(11.6)

0.36

2.63

(0.17)

11.8

(35.3)

210

210

210

6

2H

610

(288)

40.5

(11.9)

0.37

2.70

(0.17)

8.8 (26.4)

245

240

240

 

3H

704

(332)

55.3

(16.2)

0.50

3.68

(0.23)

5.2 (15.4)

320

320

320

 

4H

662

(312)

61.1

(17.9)

0.56

4.07

(0.26)

7.2 (21.5)

320

320

320

8

2H

834

(394)

52.7

(15.5)

0.48

3.51

(0.22)

4.3 (12.7)

320

320

320

 

3H

815

(385)

66.9

(19.6)

0.61

4.46

(0.28)

8.1 (24.1)

320

320

320

 

4H

775

(366)

73.7

(21.6)

0.67

4.91

(0.31)

11.3

(33.8)

320

320

320

10

2H

1029 (486)

67.0

(19.6)

0.61

4.46

(0.28)

7.3 (21.8)

415

420

410

 

3H

1117 (527)

91.0

(26.7)

0.83

6.06

(0.38)

15.9

(47.4)

530

530

530

 

4H

1057 (499)

100.0

(29.3)

0.91

6.66

(0.42)

22.3

(66.6)

530

530

530

12

2H

1175 (554)

78.0

(22.8)

0.71

5.19

(0.33)

10.3

(30.8)

490

500

490

 

3H

1242 (586)

101.5

(29.8)

0.92

6.77

(0.43)

12.8

(38.4)

530

530

530

 

4H

1181 (557)

113.0

(33.1)

1.03

7.53

(0.47)

14.9

(44.6)

530

530

530

Note:

1.CFM = Cubic feet per minute

2.TMBH = Total capacity (MBH)

3.GPM = Gallons per minute

4.WPD = Water pressure drop (feet of water)

5.Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when DT and GPM (L/s) remain constant. To determine heating capacities at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.

6.Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.

7.High static motors need the appropriate length of duct to prevent poor acoustical applications.