Performance Steam
DataCoils
Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure. All performance measured on high speed tap, zero ESP, no filter.
Table PD-10. High Static Motor, Group 1
|
|
|
|
|
| 2 psig |
|
| 5 psig |
|
|
|
|
Unit |
| CFM | TMBH |
| TMBH |
| 115V | 230V | 277V | ||||
Size | Coil | (L/s) | (TkW) | Q/ITD | (TkW) | Q/ITD | Watt | Watt | Watt | ||||
2 | Steam | 208 | (132) | 10.8 (3.2) | 0.07 | 11.5 (3.4) | 0.07 | 145 | 145 | 145 | |||
3 | Steam | 358 | (169) | 13.9 (4.1) | 0.09 | 14.7 (4.3) | 0.09 | 140 | 140 | 140 | |||
4 | Steam | 393 | (185) | 17.5 (5.1) | 0.12 | 18.5 (5.4) | 0.12 | 170 | 180 | 170 | |||
6 | Steam | 658 | (311) | 27.3 (8.0) | 0.18 | 28.9 (8.5) | 0.18 | 245 | 240 | 240 | |||
8 | Steam | 901 | (425) | 36.7 | (10.7) | 0.25 | 38.9 | (11.4) | 0.25 | 320 | 320 | 320 | |
10 | Steam | 1110 (524) | 46.4 | (13.6) | 0.31 | 49.2 | (14.4) | 0.31 | 415 | 420 | 410 | ||
12 | Steam | 1264 (597) | 54.0 | (15.8) | 0.36 | 57.2 | (16.8) | 0.36 | 490 | 500 | 490 |
Table PD-11. High Static Motor, Group 2
|
|
|
|
|
| 2 psig |
|
| 5 psig |
|
|
|
|
Unit |
| CFM | TMBH |
| TMBH |
| 115V | 230V | 277V | ||||
Size | Coil | (L/s) | (TkW) | Q/ITD | (TkW) | Q/ITD | Watt | Watt | Watt | ||||
2 | Steam | 251 | (119) | 10.4 (3.0) | 0.07 | 11.0 (3.2) | 0.07 | 145 | 145 | 145 | |||
3 | Steam | 326 | (154) | 13.4 (3.9) | 0.09 | 14.2 (4.2) | 0.09 | 140 | 140 | 140 | |||
4 | Steam | 364 | (172) | 16.9 (5.0) | 0.11 | 17.9 (5.3) | 0.11 | 170 | 180 | 170 | |||
6 | Steam | 603 | (285) | 26.3 (7.7) | 0.18 | 27.9 (8.2) | 0.18 | 245 | 240 | 240 | |||
8 | Steam | 829 | (392) | 35.5 | (10.4) | 0.24 | 37.6 | (11.0) | 0.24 | 320 | 320 | 320 | |
10 | Steam | 1024 (483) | 44.9 | (13.2) | 0.30 | 47.6 | (14.0) | 0.30 | 415 | 420 | 410 | ||
12 | Steam | 1171 (553) | 52.3 | (15.3) | 0.35 | 55.5 | (16.3) | 0.35 | 490 | 500 | 490 |
Table PD-12. Steam Properties
Steam Pressure PSIG (kPa) | 2 (14) | 5 (34) | 10 (69) | 15 (103) |
Sat. Steam Temp. F (C) | 219 (104) | 227 (108) | 239 (115) | 250 (121) |
Latent Heat — BTU/LB. (kJ/kg) | 965 (2240) | 960 (2230) | 952 (2210) | 945 (2200) |
Note:
Q/ITD = MBH (kW)/(Saturated Steam temperature - Entering air temperature) when DT and GPM remain constant. To determine heating capacities at a different saturated steam or entering air temperature, compute the new ITD and multiply it by the Q/ITD shown.steam pressure. All performance measured on high speed tap, zero ESP, with a throwaway filter.
23 |