Trane CAB-PRC001-EN manual Performance Steam DataCoils, Table PD-7.Free Discharge Motor, Group

Models: CAB-PRC001-EN

1 56
Download 56 pages 1.11 Kb
Page 22
Image 22
Performance Steam

Performance Steam

DataCoils

Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure. All performance measured on high speed tap, zero ESP, with a throwaway filter.

Table PD-7. Free Discharge Motor, Group 1

 

 

 

 

 

 

2 psig

 

 

5 psig

 

 

 

 

Unit

 

CFM

TMBH

 

TMBH

 

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(TkW)

Q/ITD

Watt

Watt

Watt

2

Steam

234

(110)

10.1 (2.9)

0.07

10.7 (3.1)

0.07

60

 

95

65

3

Steam

311

(147)

13.2 (3.9)

0.09

13.9 (4.1)

0.09

70

 

80

83

4

Steam

383

(181)

17.3 (5.1)

0.12

18.3 (5.4)

0.12

95

 

96

104

6

Steam

601

(284)

26.3 (7.7)

0.18

27.9 (8.2)

0.18

110

154

165

8

Steam

783

(370)

34.7

(10.2)

0.23

36.7

(10.8)

0.23

135

150

159

10

Steam

974

(460)

44.0

(12.9)

0.30

46.6

(13.7)

0.30

205

250

269

12

Steam

1104 (521)

51.1

(15.0)

0.34

54.2

(15.9)

0.35

230

246

263

Table PD-8. Free Discharge Motor, Group 2

 

 

 

 

 

 

2 psig

 

 

5 psig

 

 

 

 

Unit

 

CFM

TMBH

 

TMBH

 

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(TkW)

Q/ITD

Watt

Watt

Watt

2

Steam

207 (98)

9.6

(2.8)

0.07

10.1 (3.0)

0.07

60

 

95

65

3

Steam

277

(130)

12.5 (3.7)

0.08

13.3 (3.9)

0.08

70

 

80

83

4

Steam

346

(163)

16.6 (4.9)

0.11

17.6 (5.1)

0.11

95

 

96

104

6

Steam

538

(254)

25.1 (7.4)

0.17

26.6 (7.8)

0.17

110

154

165

8

Steam

702

(331)

33.1 (9.7)

0.22

35.1

(10.3)

0.22

135

150

159

10

Steam

875

(413)

42.1

(12.3)

0.28

44.6

(13.1)

0.28

205

250

269

12

Steam

993

(469)

48.9

(14.3)

0.33

51.8

(15.2)

0.33

230

246

263

Table PD-9. Free Discharge Motor, Group 3

 

 

 

 

 

 

2 psig

 

 

5 psig

 

 

 

 

Unit

 

CFM

TMBH

 

TMBH

 

115V

230V

277V

size

Coil

(L/s)

(TkW)

Q/ITD

(TkW)

Q/ITD

Watt

Watt

Watt

2

Steam

195 (92)

9.3

(2.7)

0.06

9.9

(2.9)

0.06

60

 

95

65

3

Steam

259

(122)

12.2 (3.6)

0.08

12.9 (3.8)

0.08

70

 

80

83

4

Steam

328

(155)

16.2 (4.7)

0.11

17.1 (5.0)

0.11

95

 

96

104

6

Steam

507

(239)

24.5 (7.2)

0.16

26.0 (7.6)

0.17

110

154

165

8

Steam

662

(312)

32.3 (9.5)

0.22

34.3

(10.0)

0.22

135

150

159

10

Steam

827

(390)

41.1

(12.0)

0.28

43.6

(12.8)

0.28

205

250

269

12

Steam

938

(443)

47.7

(14.0)

0.32

50.6

(14.8)

0.32

230

246

263

Note:

Q/ITD = MBH (kW)/(Saturated Steam temperature - Entering air temperature) when DT and GPM remain constant. To determine heating capacities at a different saturated steam or entering air temperature, compute the new ITD and multiply it by the Q/ITD shown.

22

CAB-PRC001-EN

Page 22
Image 22
Trane CAB-PRC001-EN manual Performance Steam DataCoils, Table PD-7.Free Discharge Motor, Group