![Standard Protections](/images/new-backgrounds/54982/5498235x1.webp)
Controls
Standard Protections
Standard Protections
The chiller controller uses
Some of the standard protection features of the chiller controller are described in this section. There are additional protection features not listed here. Contact your local Trane offi ce for additional protection information.
High Condenser-Pressure Protection
The chiller controller’s condenser limit keeps the condenser pressure under a specifi ed maximum pressure. The chiller will run up to 100 percent of this setpoint before the Adaptive Control mode reduces capacity.
Starter-Contactor Failure Protection
The chiller will protect itself from a starter failure that prevents the compressor motor from disconnecting from the line to the limits of its capabilities.
The controller starts and stops the chiller through the starter. If the starter malfunctions and does not disconnect the compressor motor from the line when requested, the controller will recognize the fault and attempt to protect the chiller by operating the
Loss of Water-Flow Protection
Tracer AdaptiViewTM control has an input that will accept a contact closure from a
flow switch be wired in series with the
Evaporator Limit Protection
Evaporator Limit is a control algorithm that prevents the chiller tripping on its low refrigerant- temperature cutout. The machine may run up to the limit but not trip. Under these conditions the intended
Low Evaporator-Water Temperature
Low
The cut out setting should be based on the percentage of antifreeze used in the customer's water loop. The chiller’s operation and maintenance documentation provides the necessary information for percent antifreeze and suggests
18 |