Controls
Standard Protections
Oil-Temperature Protection
Low oil temperature when the oil pump and/or compressor are running may be an indication of refrigerant diluting the oil. If the oil temperature is at or below the low
High
Low Differential Oil-Pressure Protection
Oil pressure is indicative of oil fl ow and active
During Compressor prelube the differential pressure should not fall below 12 psid. Shutdown diagnostic will occure within 2 seconds of the differential pressure falling below
Phase-Unbalance Protection
The following derates apply when the
10% unbalance = 100% RLA derate | 15% unbalance = 90% RLA derate |
20% unbalance = 85% RLA derate | 25% unbalance = 80% RLA derate |
30% unbalance = Shutdown |
|
Phase-Loss Protection
The controller will shut down the chiller if any of the three phase currents feeding the motor drop below 10 percent RLA. The shutdown will result in a latching
Phase Reversal/Rotation Protection
The controller detects reverse phase rotation and provides a latching diagnostic when it is detected. The time to trip is 0.7 seconds.
Momentary Power Loss and Distribution Fault Protection
An MPL has occurred when the motor no longer consumes power. An MPL may be caused by any drop or sag in the voltage that results in a change in the direction of power fl ow. Different operating conditions, motor loads, motor size, inlet guide vane (IGV) position, etc. may result in different