Trane CVHE-SVU01E-ENX39640712050 manual Constant Return, Values for start reset types, Equation

Models: CVHE-SVU01E-ENX39640712050

1 112
Download 112 pages 38.9 Kb
Page 80
Image 80

Machine Protection

and Adaptive

Control

Table 3. Values for start reset types

The values for “RESET TYPE” are:

Reset

 

Outdoor

Return

Const Return

Type:

Disable

Air Reset

Reset

Reset

 

 

The values for “RESET RATIO” for each of the reset types are:

 

Reset

Reset

Increment

Increment

Factory

Type

Ratio

English

SI Units

Default

 

Range

Units

 

Value

Return

10 to 120 percent

1 percent

1 percent

50 percent

Outdoor

-80 to 80 percent

1 percent

1 percent

10 percent

 

 

The values for “START RESET “ for each of the reset types are:

 

Reset

Start

Increment

Increment

Factory

Type

Reset

English

SI Units

Default

 

Range

Units

 

Value

Return

4 to 30°F

0.1°F

0.1°C

10°F (5.6°C)

 

(2.2 to 16.7°C)

 

 

 

Outdoor

50 to 130°F

0.1°F

0.1°C

90°F

 

(10 to 54.44°C)

 

 

(32.22°C)

The values for “MAXIMUM RESET” for each of the reset types are:

Reset

Maximum

Increment

Increment

Factory

 

Reset

English

SI Units

Default

 

Range

Units

 

Value

Return

0 to 20°F

0.1°F

0.1°C

5°F

 

(0.0 to 11.11°C)

 

 

(2.78°C)

Outdoor

0 to 20°F

0.1°F

0.1°C

5°F

 

(0.2 to 11.11°C)

 

 

(2.78°C)

Constant Return

CWS’ = CWS + 100 percent (Design Delta Temperature) - (TWE- TWL) and CWS’ > or = CWS and CWS’ -CWS < or = Maximum Reset

Notice that Constant Return is nothing more than a specific case of Return Reset offered for operator convenience.

When any type of CWR is enabled, the UCP will step the CWS toward the desired CWS (based on the above equations and setup parameters) at a rate of 1°F every 5 minutes until the Active CWS equals the desired CWS’. This applies when the chiller is running only.

Using the Equation for calculating CWR for Outdoor Air Temperature

Equation:

Degrees of Reset = Reset Ratio*(Start Reset - TOD)

The chiller will start at the Differential to Start value above a fully reset CWS or CWS for both Return and Outdoor Reset.

The graph on the next page, shows the reset function for Outdoor Air Temperature: Note: This graph assumes that Maximum Reset is set to 20 degrees.

Degrees of Reset:

Degrees of Reset = Active CWS - Front Panel CWS

or

Degrees of Reset = CWS’ - CWS

To obtain Active CWS from Degrees of Reset: Active CWS = Degrees of Reset + Front Panel CWS

(* = multiply)

80

CVHE-SVU01E-EN

Page 80
Image 80