Trane GETB Drywall Installation, Units utilizing Hinged Acoustic Door Assembly, View blow-up

Models: GETB

1 32
Download 32 pages 56.41 Kb
Page 12
Image 12
Drywall Installation

Installation

Drywall Installation

Before installing drywall around cabi- net. Cover the cabinet supply and re- turn openings with plastic or cardboard to help prevent dust or con- struction debris from reaching unit components. Warranties will be void- ed if paint or foreign debris is allowed to contaminate internal unit compo- nents.

The location of the drywall may be de- pendent upon the type of return air ac- cess design.

1Units that contain a field provided return air access assembly, contrac- tor must calculate location of dry- wall to allow for frame mounting.

Units utilizing Hinged Acoustic Door Assembly.

1 Locate the side studs a minimum of

1 1/4-inches and a maximum of 1 3/

4Place the door frame into the sheet rock opening. A positive seal is critical be- tween the back of the door frame and the front of the cabinet. Ensure that the gasket material seals properly. Note: When placing the sheet rock panel, make certain the opening for the door is centered with the return-air opening in the cabinet (±1/8").

 

3 1/2” ±3/8”

 

 

A

 

 

2“ X 4” STUD

 

 

 

 

SHEETROCK

 

1 1/4” +1/2”/-0”

 

 

 

 

B

 

 

 

 

 

1“ X 1” CLOSED

 

RETURN AIR OPENING

 

CELL INSULATION

 

 

 

 

FLANGE ON CABINET

CABINET

 

 

RETURNAIR FLANGEDOOR

A

 

 

 

SHEET ROCK

 

 

1“ X 1” CLOSED

OPENING

RETURN AIR OPENING

 

 

CELL INSULATION

 

FLANGE ON CABINET

 

 

8-inches from the cabinet to the side

of the stud. This critical dimension,

combined with "distance between

studs" is used to determine the side-

to-side opening for the door, dimen-

sion A. The distances provided in

the table are a "minimum" dimen-

sion. Allow 3 1/2-inches from the

front of the cabinet to the sheet rock

surface, Figure 4 - Top View. Figure

5, mock-up of stud placement.

2 The height of the door assembly

must be positioned to recess the

door 2 1/4-inches from the cabinet’s

return-air opening, Figure 4 - Side

View blow-up.

3 Locate dimensions A and B for sheet

rock opening size. The position of

the sheet rock opening must be cen-

tered side-to-side with the return-air

opening in the cabinet. Ensure the

bottom of the sheet rock opening is

2 1/4-inches below the return-air

opening in the cabinet. This allows

the door recess to rest on the bot-

tom of the sheet rock opening for

proper vertical placement of the

door.

Unit Size

A

B

 

 

 

09

19 1/4”

44 1/8”

 

 

2“ X 4”

012

(489)

(1121)

SHEETROCK

 

 

 

STUD

015

23 1/4”

45 1/4”

 

 

 

018

(591)

(1149)

 

 

 

024

27 1/8”

54 5/8”

 

Note:

 

 

Finished wall and framing should not

036

(689)

(1387)

 

 

touch the unit cabinetry.

 

 

 

 

 

 

 

 

 

 

 

CABINET

 

3 1/2” ±3/8”

 

 

 

 

SHEETROCK

 

 

 

 

 

RETURN AIR

 

 

 

 

 

DOOR FRAME

 

2 X 4 STUD

 

 

 

 

 

 

 

 

1“ X 1” CLOSED

 

RETURN-AIR OPENING

 

 

 

FLANGE ON CABINET

 

 

CELL INSULATION

 

 

 

 

 

 

 

 

 

 

 

B

 

 

1“ X 1” CLOSED

 

RETURN-AIR OPENING

 

 

CELL INSULATION

 

FLANGE ON CABINET

 

 

RETURN AIR

 

 

 

 

 

DOOR FRAME

 

2 1/4“

5“

 

 

 

 

 

 

 

 

4 5/8“

 

 

SHEETROCK

 

 

 

 

 

 

 

 

 

FLOOR

 

CABINET

 

 

 

1 1/2” X 2 3/8”

3 1/2” ±3/8”

 

 

 

 

 

 

 

 

 

SIDE VIEW

1 1/4” +1/2”/-0”

TOP VIEW

Figure 5:

Figure 4: Drywall installation for hinged acoustic door

12

WSHP-SVN08B-EN

Page 12
Image 12
Trane GETB manual Drywall Installation, Units utilizing Hinged Acoustic Door Assembly, surface, - Top View. Figure