Installation
Low Voltage Wiring
Low Voltage Wiring
Factory ordered thermostats and zone sensors are
1After installing the cabinet assem- bly, simply plug the male portion of thermostat/zone sensor plug into the female portion of the plug locat- ed inside the unit’s junction box.
2Mount the thermostat or zone sen- sor on the finished drywall.
Thermostat/zone sensor connection is shown in Figure 13.
Low Voltage Wiring for Field Provided Thermostats/Zone Sensors
Ensure that the AC control wiring be- tween the controls and the unit’s ter- mination point does not exceed three
(3)ohms/conductor for the length of the run.
Note: Resistance in excess of
Check all loads and conductors for grounds, shorts, and
Use copper conductors unless other- wise specified.
Do not run the AC low voltage wiring in the same conduit with the high volt- age power wiring.
Table 4: 24V AC conductors
Distance from unit | Recommended |
to Control | Wire Size |
|
|
18 gauge | |
|
|
16 gauge | |
|
|
14 gauge | |
|
|
Factory provided plug
Six (6) Pin Connector/Harness
Red = 24V
Black = Fan
Orange = RV
Yellow = Compressor
Blue = Common
Figure 13: Zone sensor connection
Table 5: Deluxe controller diagnostic LEDs
Color: Green | Color: Red | Controller Mode | |
|
|
| |
LED1 | LED2 | LED3 |
|
|
|
|
|
OFF | OFF | OFF | Control OFF |
|
|
|
|
ON | OFF | OFF | Normal/Compressor OFF |
|
|
|
|
ON | OFF | FLASH | |
|
|
|
|
ON | OFF | ON | Normal/Compressor ON |
|
|
|
|
FLASH | ON | OFF | Brownout Condition |
|
|
|
|
ON | FLASH | ON | Soft Lockout (low pressure) |
|
|
|
|
ON | FLASH | FLASH | Soft Lockout (high pressure) |
|
|
|
|
ON | ON | ON | Manual Lockout (low pressure) |
|
|
|
|
ON | ON | FLASH | Manual Lockout (high pressure) |
|
|
|
|
ON | FLASH | OFF | Manual Lockout (condensate overflow) |
|
|
|
|
ON | ON | OFF | Compressor Disable |
|
|
|
|
16 |