NETWORKING

AdaptAire is adaptable to a variety of different network architectures and protocols. Each controller has built-in protocol translation and can be configured for operation on ARCnet156 or EIA-485 communication networks. See Appendix IV for specific controller specifications.

The AdaptAire system can be connected to most existing building automation systems. Some systems may require the use of special controllers and network communication devices. See Appendix I for Device Parameters and Cache Setup information.

ADAPTAIRE DEFAULT SETTINGS

The following is a list of AdaptAire DDC controller defaults. These are the default operating parameters set at the factory prior to shipment.

Table 1.

Default settings

 

 

 

 

 

 

 

ITEM

DEFAULT

RANGE

 

 

 

Unit Network Address

002 binary dips

000 – 255 binary dips

 

 

 

Unit Operating Mode

OFF

OFF – MANUAL - AUTO

 

 

 

Time Clock Schedule

None

4 Daily - 12 Holiday - 2

 

 

 

Override schedules

 

 

 

Heating/Cooling Operating

Heating

HEATING - COOLING

 

Mode

 

 

 

 

 

Damper Operating Mode

Manual

MANUAL - BUILDING

 

 

 

PRESS - MIXED AIR

 

 

 

TEMP

 

 

 

Fuel Selection

Natural Gas

NATURAL - PROPANE

 

 

 

Heating Night Setback

55°F

40°F - 80°F

 

 

 

Cooling Night Setback

100°F

75°F - 120°F

 

 

 

Room Temperature Setpoint

65°F

55°F - 90°F

 

 

 

 

 

Freezestat

45°F

35°F - 50°F

 

 

 

Outside Air Economizer

65°F

40°F - 80°F

 

Setpoint

 

 

 

 

 

Minimum Discharge

55°F

40°F - 130°F

Temperature Setpoint

 

 

 

 

 

Maximum Discharge

100°F

55°F - 130°F

Temperature Setpoint

 

 

 

 

 

Mixed Air Temperature

50°F

30°F - 90°F

 

Setpoint

 

 

 

 

 

Building Pressure Setpoint

0” W. C.

-0.05” - +0.05” W. C.

 

 

 

Manual Damper Position

20% Outside Air

0% - 100%

 

Setpoint

 

 

 

 

 

Minimum Ventilation

20% Outside Air

0% - 100%

 

Setpoint

 

 

 

 

 

User PID Select

Direct Acting

DIRECT -REVERSE

 

 

 

High Input Value

0

-9999.99 – 99999.99

 

 

 

 

MUA-SVP01A-ENDirect-Fired Indoor and Outdoor Units

3

Page 3