I/O Zone 583 Controller Specifications

LED indication

3 Analog Outputs

0 - 10 VDC

OUTPUT ASSIGNMENTS - ANALOG

AO1

Burner firing rate (to signal conditioner) 0 - 10 VDC

AO2

RA or Mixing Damper Control/ User Configured 0 - 10VDC

AO3

Unassigned

OUTPUT ASSIGNMENTS - DIGITAL

DO1 Unit Enable

DO2 Burner Enable

DO3 Cooling Enable

DO4 Alarm

DO5 Pilot to Main Flame Sensor Changeover Switch

INPUT ASSIGNMENTS - UNIVERSAL

IN1

Pressure Transducer for Building Pressure Control or User Configured

IN2 Pressure Transducer for Flow Station

IN3

Multiplexed

100% Outside Air/100% Output

Flame Failure Alarm

Safety Circuit Status

Manual/Mixed Air Dmpr Control

IN4 Multiplexed

Auxiliary Unit Enable

Clogged Filter

Fan Status

Burner Status

IN5 Outside Air sensor

IN6 Discharge Air sensor

IN7 Unit Enable/Remote Setpoint

IN8 Damper Control

RNET MRT-Pro or Room Air sensor

52

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Page 52
Image 52
Trane MUA-SVP01A-EN manual Zone 583 Controller Specifications, Rnet MRT-Pro or Room Air sensor