Direct-Fired Indoor and Outdoor Make-Up Air Units, MUA-SVP01A-EN
FUEL SELECT HOTKEY - 9
1
48
58
58
Download
58 pages, 1.42 Mb
48
Direct-Fired Indoor and Outdoor Units •
MUA-SVP01A-EN
Menu Selection
Alarm
Fuel Select
FUEL SELECT HOTKEY - 9
Fuel Type
Natural Gas/Propane
Login
Home
Previous
Unit Modes
Contents
Main
Overview
NETWORKING
ADAPTAIRE DEFAULT SETTINGS
Page
Contents
Unit Operating Modes
Functions
Diagnostics
Menu Selection
Contents
Thermostat Output Curve
Airflow Station Layout I/O Zone 583 Controller Specifications Typical Wiring Schematic
Unit Operating Modes
MDT Controls:
MRT Controls:
MRT-Pro Controls:
Page
MRT-Expert Controls:
Page
Heating/Ventilating/Cooling Operating Modes
Heating Mode
General Burner Control
Page
Ventilation Mode
Cooling Mode
Figure 1. Cooling Mode
Damper Control Modes
Manual Mode
Mixed Air Temperature Mode
Building Pressure Mode
Functions
100% Outside Air
Minimum Ventilation
Freezestat
Clogged Filter
User Configured PID Control
DIRECT ACTING
Page
REVERSE ACTING
Page
Unit Resets
Multiplexed Inputs
Clock Set
Diagnostics
Critical Fault Codes
FAULT CODE: Low Discharge Temperature
Page
SOLUTION: If burner was not operating prior to shutdown (check prior alarm log)
FAULT CODE: Safety Circuit Open
SOLUTION:If fan is running (check prior alarm log)
FAULT CODE:Burner Status
FAULT CODE: Burner Hand
FAULT CODE: Flame Failure
Diagnostics - Non-Critical Fault Codes
FAULT CODE: Unit off/Fan on
SOLUTION: If fan is running
SOLUTION: If fan is not running
FAULT CODE:Unit on/Fan off
SOLUTION:If fan/motor is running
SOLUTION: If fan/motor is not running
FAULT CODE: Check Airflow Switches
SOLUTION:If high airflow switch is opening. Do not adjust the switch setpoints
SOLUTION:If low airflow switch is opening. Do not adjust the switch setpoints
FAULT CODE: Clogged Filter Switch
SOLUTION:If clogged filter switch is closing.
FAULT CODE:Energy Save Mode 1
SOLUTION:If setpoints are misadjusted
SOLUTION:If setpoints are not misadjusted
FAULT CODE:Energy Save Mode 2
SOLUTION: If OAT, RoomT or DAT are such that heat is required
FAULT CODE:Energy Save Mode 3
SOLUTION: If OAT, RoomT or DAT are such that heat is required
SOLUTION: If setpoints are misadjusted
FAULT CODE:Insufficient OA
SOLUTION:If heat is desired
SOLUTION:If less outside air is desired
Page
Menu Selection Tree for BACview
UNIT MODES HOTKEY - 2
Menu Selection
Status Alarm
SET POINTS HOTKEY - 3
STATUS MENU HOTKEY - 4
Note: The Status Menu always displays the current status of the fan, burner and cooling.
ALARM HOTKEY - 1
Alarm History (64 Most Recent)
RESETS HOTKEY - 6
SCHEDULES HOTKEY- 7
USER CONFIGURABLE OUTPUT HOTKEY - 8
CLOCKSET HOTKEY - 0
HELP HOTKEY - 5
FUEL SELECT HOTKEY - 9
10 K Ohms Thermistor Output Curve
Thermostat Output Curve
Resistance (Ohms)
Typical 10,000 Ohm Thermistor Output Curve
Resistance (Ohms)
Typical 10,000 Ohm Thermistor Output Curve
Page
I/O Zone 583 Controller Specifications
I/O Zone 583 Controller Specifications
OUTPUT ASSIGNMENTS - ANALOG
RNET MRT-Pro or Room Air sensor
OUTPUT ASSIGNMENTS - DIGITAL
INPUT ASSIGNMENTS - UNIVERSAL