Trane TSD To increase airflow, To decrease airflow, To adjust belt, Motor sheave / Fan speed

Models: TSD TSH 060

1 68
Download 68 pages 32.16 Kb
Page 15
Image 15

Installation

To increase airflow

Loosen variable sheave set screw and turn sheave clockwise.

To decrease airflow

Loosen variable sheave set screw and turn sheave counter-clockwise.

To adjust belt

The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn.

Units with dual belts require a matched set of belts to ensure equal belt length.

When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.

Once the new belts are installed, adjust the belt tension.

Table 8 - Motor sheave / Fan speed

 

 

 

 

Fan speed (RPM)

 

 

 

 

 

 

 

Standard drive & motor

 

 

 

 

 

 

 

 

 

 

 

Unit

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

Closed

Open

Open

Open

Open

Open

Open

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

N/A

898

967

1036

1105

1174

1243

 

 

 

 

 

 

 

 

TSD/TSH 072

N/A

698

751

806

859

913

967

 

 

 

 

 

 

 

 

TSD/TSH 090

N/A

752

806

860

914

968

1020

 

 

 

 

 

 

 

 

TSD/TSH 102

N/A

688

737

786

835

885

934

 

 

 

 

 

 

 

 

TSD/TSH 120

N/A

782

838

894

950

1006

1062

 

 

 

 

 

 

 

 

YSD/YSH 060

N/A

1036

1105

1174

1243

1312

1381

 

 

 

 

 

 

 

 

YSD/YSH 072

N/A

806

860

913

968

1022

1074

 

 

 

 

 

 

 

 

YSD/YSH 090

859

913

967

1021

1075

1129

N/A

 

 

 

 

 

 

 

 

YSD/YSH 102

786

836

885

934

982

1032

N/A

 

 

 

 

 

 

 

 

YSD/YSH 120

894

950

1006

1062

1118

1174

N/A

 

 

 

 

 

 

 

 

WSD/WSH 060

N/A

898

967

1036

1105

1174

1243

 

 

 

 

 

 

 

 

WSD/WSH 072

N/A

698

751

806

859

913

967

 

 

 

 

 

 

 

 

WSD/WSH 090

N/A

752

806

860

914

968

1020

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed (RPM)

 

 

 

 

 

 

 

Oversized drive & motor

 

 

 

 

 

 

 

 

 

 

 

Unit

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

Closed

Open

Open

Open

Open

Open

Open

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

N/A

1243

1311

1379

1450

1515

1588

 

 

 

 

 

 

 

 

TSD/TSH 072

N/A

967

1021

1075

1128

1183

1235

 

 

 

 

 

 

 

 

TSD/TSH 090

1112

1182

1252

1322

1392

1460

N/A

 

 

 

 

 

 

 

 

TSD/TSH 102

N/A

971

1041

1111

1181

1251

1321

 

 

 

 

 

 

 

 

TSD/TSH 120

1062

1118

1174

1229

1285

1341

N/A

 

 

 

 

 

 

 

 

YSD/YSH 060

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

YSD/YSH 072

N/A

967

1021

1075

1128

1183

1235

 

 

 

 

 

 

 

 

YSD/YSH 090

1112

1182

1252

1322

1392

1460

N/A

 

 

 

 

 

 

 

 

YSD/YSH 102

N/A

971

1041

1111

1181

1251

1321

 

 

 

 

 

 

 

 

YSD/YSH 120

1062

1118

1174

1229

1285

1341

N/A

 

 

 

 

 

 

 

 

WSD/WSH 060

N/A

1243

1311

1379

1450

1515

1588

 

 

 

 

 

 

 

 

WSD/WSH 072

N/A

967

1021

1075

1128

1183

1235

 

 

 

 

 

 

 

 

WSD/WSH 090

1112

1182

1252

1322

1392

1460

N/A

 

 

 

 

 

 

 

 

RT-SVX20A-E4

15

Page 15
Image 15