Controls
Trane THS01,THS02, THP01 and THP02 Thermostats are directly connected to RTRM board (J7 connector).
Trane THS03 and THP03 thermostats are directly connected to RTRM board (J6 connector).
Install the electrical link between the thermostat (thermostat terminal strip) and the unit (J6 or
J7 connector) in compliance with the interconnection diagram. The low voltage wiring must not be laid in the same pipes as the power cables.
The sizes and lengths of the thermostat connection wires are given in Table 39. The total resistance of these control cables must not exceed 5 ohms. If the resistance exceeds this value the thermostat may not operate with the same precision.
Table 39 - Zone sensor wire and maximum length
Wire size | Maximum | |
wire lengh | ||
(mm²) | ||
(m) | ||
| ||
|
| |
0,33 | 45 | |
|
| |
0,5 | 76 | |
|
| |
0,75 | 115 | |
|
| |
1,3 | 185 | |
|
| |
2 | 300 | |
|
|
Unit controlled by BAS
Each unit must be equipped with a
Unit controlled by Tracker™ supervisor
The units must also be equipped with the
34 |