Trane TSD Unit wiring, Ampacity Size, Ph/Hz Without Electric heat option, With Electric heat

Models: TSD TSH 060

1 68
Download 68 pages 32.16 Kb
Page 31
Image 31

Installation

The "ABC" indicator on the face of the phase indicator will glow if phase is ABC for terminals L1, L2, L3.

IMPORTANT! After completion of wiring, check all electrical connections, and ensure all connections are tight. Replace and secure all electrical box covers and access doors before leaving unit or connecting power to circuit supplying the unit.

CAUTION! Units with scroll compressors are not equipped with crankcase heaters.

WARNING! Disconnect all power, including remote disconnects, and discharge all capacitors before servicing.

Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. After power is removed, allow

4 minutes for capacitors to discharge. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and/or discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see Trane Service Bulletin PROD-SVB06A.

Table 36 - Unit wiring

 

 

Standard Supply Fan Motor

Oversized Supply Fan Motor

 

 

 

 

 

 

 

Main power

Minimum Circuit

Maximum Overcurrent

Minimum circuit

Maximum Overcurrent

Unit Model

Protective Device (Fuse

Protective Device (Fuse

supply

Ampacity

ampacity

and size

or Circuit Breaker)

or Circuit Breaker)

(V/Ph/Hz)

(A)

(A)

 

(A)

(A)

 

 

 

 

 

 

 

 

 

 

Without Electric heat option

 

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

400/3/50

18,2

32

19,3

32

TSD/TSH 072

400/3/50

24,4

32

25,5

32

TSD/TSH 090

400/3/50

26,2

40

27,2

40

TSD/TSH 102

400/3/50

28,3

40

29,3

40

TSD/TSH 120

400/3/50

32,6

40

32,6

40

 

 

 

 

 

 

YSD/YSH 060

400/3/50

18,2

32

-

-

YSD/YSH 072

400/3/50

24,4

32

25,5

32

YSD/YSH 090

400/3/50

26,2

40

27,2

40

YSD/YSH 102

400/3/50

28,3

40

29,3

40

YSD/YSH 120

400/3/50

32,6

40

32,6

40

 

 

 

 

 

 

WSD/WSH 060

400/3/50

20,1

32

21,2

32

WSD/WSH 072

400/3/50

23,1

32

24,2

32

WSD/WSH 090

400/3/50

26,2

40

27,2

40

 

 

 

 

 

 

With Electric heat

 

 

 

 

 

 

 

 

 

 

 

TSD/TSH 060

400/3/50

26,4

50

27,5

50

TSD/TSH 072

400/3/50

37,8

50

38,9

50

TSD/TSH 090

400/3/50

39,2

50

40,2

50

TSD/TSH 102

400/3/50

50,1

63

51,1

63

TSD/TSH 120

400/3/50

51,8

63

51,8

63

 

 

 

 

 

 

WSD/WSH 060

400/3/50

40,8

50

41,9

50

WSD/WSH 072

400/3/50

55,2

63

56,3

63

WSD/WSH 090

400/3/50

58,3

63

59,3

63

 

 

 

 

 

 