Trane YCZ036F1/3M0B manual Condensate Drain Piping, Typical Ground Level Application, Installation

Models: YCZ036F1/3M0B YCZ035F1

1 24
Download 24 pages 41.31 Kb
Page 11
Image 11
GROUND LEVEL -- HORIZONTAL UNITS

INSTALLATION

GROUND LEVEL -- HORIZONTAL UNITS

For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure (See Figure 11.) Be sure the outdoor portion of the supply and return air ducts are as short as possible.

Proceed with the installation as follows:

1.Place the unit on the pad and the five (5) rubber isolators provided.

2.Attach the supply and return air ducts to the unit.

3.Insulate any ductwork outside of the structure with at least 2 inches of insulation and weatherproof. There must be a weather- proof seal where the duct enters the structure.

4.Complete the installation according to the instructions in the following sections of this manual.

q

TYPICAL GROUND LEVEL APPLICATION

 

(YCZ036,050,060F MODELS)

 

 

 

 

 

OUTDOOR AIR

 

 

 

DISCHARGE

 

 

SUPPLY AIR

 

 

RETURN AIR

DUCT

 

 

DUCT

 

 

SIDING

 

 

 

 

 

 

OUTDOOR AIR

 

 

 

INTAKE

 

 

 

FLUE

 

 

 

INLET HOOD

 

 

 

SUPPORT PAD

 

 

 

FOUNDATION

EXTERIOR

 

 

 

WALL

 

 

 

 

INSULATE

FLEXIBLE DUCT

ISOLATORS

 

WEATHERPROOF

 

CONNECTORS

(1 PER CORNER

 

OR RAIN SHIELD

 

 

AND 1 UNDER

 

 

 

UNIT CONTROL BOX)

CONDENSATE DRAIN PIPING

A 3/4-inch female NPT condensate drain connection is provided on the evaporator access panel end of the unit. See Figure 4. Provide a trap and fill it with water before starting the unit to avoid air from being drawn through. Follow local codes and standard piping practices when running the drain line. Pitch the line downward away from the unit. Avoid long horizontal runs. See Figure 12.

NOTE: Do not use reducing fittings in the drain lines. The condensate drain must be:

Made of 3/4" pipe size.

Pitched 1/4" per foot to provide free drainage to convenient drain system.

wTYPICAL CONDENSATE DRAIN PIPING

3/4" PVC OR COPPER TUBING AND FITTINGS

1-1/2" MIN.

Trapped.

Must not be connected to closed drain system.

Page 11

Page 11
Image 11
Trane YCZ036F1/3M0B manual Condensate Drain Piping, Typical Ground Level Application, YCZ036,050,060F MODELS, Installation