CONVERTING HORIZONTAL TO DOWNFLOW

5

NOTE

SUPPLY OPENING

1.REMOVE SCREW NEAREST TO THE OPENING AND PULL THE PANEL FIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT.

RETURN OPENING

2.REMOVE RIGHT HAND SCREW AND MOVE PANEL TO THE RIGHT OR RE- MOVE BOTH SCREWS.

CONVERTING HORIZONTAL TO DOWNFLOW

HEATER EXCHANGER

TUBES

SHEET METAL

HORIZONTAL RETURN

SCREWS

AIR COVER

HORIZONTAL SUPPLY

AIR COVER

6

REQUIRED CLEARANCE FOR UNIT INSTALLATION

 

 

AND ROOF PENETRATION HOLE SIZE REQUIRED

D

SERVICE

CLEARANCE

LINES

SIDE RAIL

WOOD NAILER

SERVICE CLEARANCE & PENETRATION DIMENSIONS

MODEL NO.

A

B

C

D

E

F

 

 

 

 

 

 

 

YCZ036F

30"

30"

*12"

30"

44"

25"

 

 

 

 

 

 

 

YCZ050F

42"

30"

*12"

36"

50"

25"

YCZ060F

 

 

 

 

 

 

*18" WITH FRESH AIR ACCESSORY

*30" WITH ECONOMIZER